15-62

Chapter 15: Appendix

15

[5] Wiring and grounding through wiring ducts and conduits

Shown below are methods for wiring and grounding through wiring ducts and conduits used on an FL-
net.
Observe the precautions below when wiring
1. When wiring using wiring ducts, separate the power lines and signal lines using a physical separator.

The wiring duct itself (including the lid and separator) must be grounded with a class D ground.

2. When using conduits, provide one conduit for the power lines and one for the signal lines. Use

conduit that complies with JIS-C-8305 and create a class D ground.

Wiring example when using a wiring duct

Wiring example using a conduit

Class D ground

Separator

Communication
cable

Analog I/O signal lines

I/O signal lines

Power lines

Wiring duct

Signal cable

Conduit

Class D ground

Advertising