15 technical data, Technical data – Studer Innotec XTH 3000-12 User Manual

Page 37

Advertising
background image

Steca

Xtender

Installation and Operating Instructions 723.932 Xtender V0.511

Seite 37

15 Technical data

Model

XTH 3000-12

XTH 5000-24

XTH 6000-48

XTH 8000-48

Inverter

Rated battery voltage

12 V

24 V

48 V

48 V

Input voltage range

9.5 - 17 V

19 - 34 V

38 - 68 V

39 - 68 V

Continuous power @ 25 °C

2,500 VA

4,000 VA

5,000 VA

7,000 VA

Smart boost power

2,500 VA

4,000 VA

5,000 VA

7,000 VA

30 minute charge @ 25 °C

3,000 VA

5,000 VA

6,000 VA

8,000 VA

5 second charge @ 25 °C

3 x Pnom

Maximum charge

Up to short-circuit

Maximum asymmetrical charge

Up to Pnom

Load detection (standby)

2 to 25 W

Admissible cos phi

0.1 – 1

Maximum efficiency

93% 94% 96% 96%

Open-circuit power
OFF/standby/ON

1.7 W/2.2 W/14

W

1.8 W/2.5 W/20

W

2.2 W/3 W/22 W 2.2 W/3.8 W/34

W

Output voltage

230 Vac (-10% /0)

Output frequency

50/45-65 Hz +/- 0.05% (quartz-controlled)

Harmonic distortion

<2%

Dynamic correction

0.5 ms (charge leap from 0 to 100%)

Overcharge and short-circuit

Automatic disconnection then 2 startup attempts

Overheating protection

Alarm prior to disconnection and automatic restart

Battery charger

6-phase battery charger

Programmable I-U-Uo-equalisation-Uo(low)-U(periodic)

Adjustable charge current

0 - 160 A

0 - 140 A

0 - 100 A

0 - 120 A

Input current sharing system

1 - 30 A

1 - 50 A

Maximum input voltage

265 Vac

AC input voltage range

Level of detection adjustable from 150 to 230 Vac

Admissible input frequency

45 - 65 Hz

(PFC)

EN 61000-3-2

Battery control (factory value / adjustable range with RCC-02)

End of absorption

by duration 4 / 0.25 - 10 h or by current - / 4 - 30 A

Absorption voltage

14.4 / 9.5 - 18 V 28.8 / 19 - 36 V

57.6 / 38 - 72 V

Periodic absorption voltage

- / 9.5 - 18 V

- / 19 - 36 V

- / 38 - 72 V

Maintenance voltage

13.6 / 9.5 - 18 V 27.2 / 19 - 36 V

54.4 / 38 - 72 V

Reduced maintenance voltage

- / 9.5 - 18 V

- / 19 - 36 V

-- / 38 - 72 V

Equalisation

End of equalisation

Equalisation voltage

- / 9.5 - 18 V

- / 19 - 36 V

- / 38 - 72 V

10.8 / 9.5 - 18 V 21.6 / 19 - 36 V 43.2 / 38 - 72 V

- / 0 - 32 days

- / 0 - 10 hours

Temperature compensation

-5 / 0 to-8 mV/°C/cell (optional BTC-01)

General data

Auxiliary contacts

2 independent contacts 16 A - 250 Vac (potential-free 3 points)

Maximum transfer relay current

30 A

50 A

Maximum transfer time

<25 ms

Weight

34 kg

40 kg

42 kg

46 kg

Dimensions: H x W x D [mm]

220x290x500

220x310x500

Protection degree

IP23

Conformity

EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2,

Dir. 89/336/EEC, LVD 73/23/EEC

Operating temperature range

-20 to 55 °C

Ventilation

Forced from 45 °C

Noise level

<35 dB / <50 dB (without / with ventilation)

Warranty

2 years

Options

Battery temperature sensor :

BTS-01

Remote control and programming centre: RCC-02 / RCC-03

Advertising