Sentric switch disconnectors, General data – Siemens AC-21A User Manual

Page 12

Advertising
background image

Siemens LV 10 · 2004

7/12

SENTRIC Switch Disconnectors

General data

SENTRIC K Switch Disconnectors from 63 A to 1000 A

7

Technical specifications

1) Technical specifications for CSA approval on request.

2) Configuring note: max. permissible operating temperature at connections

100 °C.

3) With 3KA58 for operation –25 °C ... +35 °C, 570 A at 55 °C.

4) Only for 3NA38, 3NA32 or 3ND18, 3ND12 fuses (105 kA/50 kA for others).

5) 3ND1 switchgear protection fuses.

6) AC-23B.

7) At 440 V L/R = 4 ms, at 220 V L/R = 15 ms.

8) At 440 V DC-22A, at 220 V DC-23A.

Standards

IEC 60947-1, IEC 60947-3, VDE 0660 Part 107

Type

3KA50

3KA51

3KA52

3KA53

1)

3KA55

3KA57

1)

3KA58

Rated uninterrupted current I

u

A

63

80

125

160

250

400

630

3)

Continuous thermal current I

th

2)

A

63

80

125

160

250

400

630

3)

Rated insulation voltage

U

i

V

690

690

1000

1000

1000

1000

1000

Rated impulse withstand voltage

U

imp

kV

6

6

8

8

8

8

8

Rated operating voltage

U

e

AC 50 Hz/60 Hz

V

690

DC

V

440 (3 conducting paths series-connected),
220 (2 conducting paths series-connected)

Rated short-circuit making capacity
with back-up fuses

4

)

at AC 50 Hz/60 Hz 690 V

kA (peak value)

220

220

220

220

220

220

220

Rated conditional short-circuit current with series-
connected fuses

4

)

at AC 50 Hz/60 Hz 690 V

kA (rms value)

100

100

100

100

80

80

50

Max. rated current I

n

of the fuses

A

63

80

160

160

400

400

630

Permissible let-through current of the fuses

kA

8

10

17

17

30

5)

30

5)

40

5)

Maximum permissible let-through I

2

t value

kA

2

s

55

55

223

223

1000

1000

2600

Permissible let-through current of a series-con-
nected circuit-breaker
at AC 50 Hz/60 Hz 690 V

kA (peak value)

7

8

8

15

25

25

32

Rated short-circuit making capacity
without fuses
at AC 50 Hz/60 Hz 690 V

kA (peak value)

7

7

7

9

20

25

35

Switching capacity (infeed top or bottom)

at AC 400 V
Breaking current I

c

(p.f. = 0.35)

A (rms value)

500

650

1000

1280

2000

3200

5040

Rated operating current I

e

at

AC-21A, AC-22A, AC-23A

A

63

80

125

160

250

400

630

6)

Motor switching capacity at AC-23A

kW

30

40

65

80

132

200

350

At AC 500 V
Breaking current I

c

(p.f. = 0.35)

A (rms value)

500

640

1000

1280

2000

3200

3200

Rated operating current I

e

at

AC-21A, AC-22A
AC-23A

A
A

63
63

80
80

125

160
160

250
250

400
400

630
400

6)

Motor switching capacity at AC-23A

kW

40

50

90

110

185

280

280

at AC 690 V
Breaking current I

c

(p.f. = 0.35)

A (rms value)

500

500

1000

1280

2000

3200

3200

Rated operating current I

e

at

AC-21A, AC-22A
AC-23A

A
A

63
63

80
63

125
125

160
160

250
250

400
400

630
400

6)

Motor switching capacity at AC-23A

kW

50

50

110

150

220

375

375

at DC 440 V (3 conducting paths connected in series)
Breaking current I

c

(L/R = 15 ms)

A

250

260

500

640

1000

7)

1600

1600

Rated operating current I

e

at DC-23A

A

63

63

125

160

250

8)

400

400

Rated short-time current (1 s current)

kA (rms value)

2.5

2.5

3.2

3.2

8

11

15

Permissible load
depending on the ambient temperature for open-type
installation in switchboards (e.g. 8NA1) in switchgear
cubicles or switchgear racks at
35 °C

A

63

80

125

160

250

400

630

40 °C

A

63

80

125

160

250

400

620

45 °C

A

63

80

125

160

250

400

600

50 °C

A

63

80

125

160

250

400

580

55 °C

A

63

80

125

160

250

400

560

60 °C

A

63

80

125

160

250

400

550

Permissible ambient temperature

°C

–25 ... +55 for operation, –50 ... +80 for storage

3)