Section 4 Air Requirements

4.11 Block Heaters

Block heaters are recommended on all standby
applications

where

the

generator

is

subject

to

temperatures below 60

° F (16°C) and are available as

installed accessories on all generator sets. The block
heater should be connected to a source of power, which
is determined by the particular size and type of heater.

Note: BLOCK HEATER DAMAGE! Do not energize block

heater until engine block is filled with coolant and the
generator set is run to remove trapped air.
Otherwise, block heater failure will result. Unplug
block heater prior to draining cooling system.

4.12 Recommended Coolant

Antifreeze/coolant protection will be required for most
applications. This must be performed prior to startup of
generator set and energizing block heater(s).

A solution of 50% ethylene glycol and 50% clean,
softened water is recommended to provide freezing
protection to --34

°F (--37°C) and boiling protection to

256

°F (129 °C). A 50/50 solution will also inhibit rust and

corrosion.

Follow

the

engine

manufacturer’s

recommendations when available.

For most diesel engines, an additional inhibitor additive
is required to prevent cavitation erosion. Refer to the
engine operation manual for inhibitor section and
concentration level recommendations.