Troubleshooting, Start up conditions, Operational conditions – Kenmore POWER MISER 153.326265 User Manual

Page 23

Advertising
background image

23

Start Up Conditions

THERMAL EXPANSION

Water supply systems may, because of such events as high
line pressure, frequent cut-offs, the effects of water hammer
among others, have installed devices such as pressure reducing
valves, check valves, back flow preventers, etc...to control these
types of problems. When these devices are not equipped with
an internal by-pass, and no other measures are taken, the
devices cause the water system to be closed. As water is heated,
it expands (thermal expansion) and closed systems do not allow
for the expansion of heated water.

The water within the water heater tank expands as it is heated
and increases the pressure of the water system. If the relieving
point of the water heater's temperature-pressure relief valve is
reached, the valve will relieve the excess pressure. The
temperature-pressure relief valve is not intended for the
constant relief of thermal expansion.
This is an unacceptable
condition and must be corrected.

It is recommended that any devices installed which could create
a closed system have a by-pass and/or the system have an
expansion tank to relieve the pressure built by thermal expansion
in the water system. Thermal expansion tanks are available from
Sears stores and through the Sears Service Centers. Contact the
local plumbing inspector, water supplier and/or the Sears Service
Center for assistance in controlling these situations.

Thermal Expansion Tank Specifications

Tank Dimensions

Pipe

Model

Capacity in Inches

Fitting

Number

In Gallons

Diameter

Length

On Tank

153.331020

2

8 (203 mm) 12-3/4 (323 mm) 3/4” Male

153.331050

5

11 (279 mm) 14-3/4 (375 mm) 3/4” Male

Expansion Tank Sizing Chart

Inlet* Water Heater Capacity (Gallons)

Water

Pressure

30

40

50

66

82

Expansion

40psi

2

2

2

5

5

Tank

50psi

2

2

2

5

5

Capacity

60psi

2

2

5

5

5

Needed

70psi

2

2

5

5

5

80psi

2

5

5

5

5

*Highest recorded inlet water pressure in a 24 hour period or
regulated water pressure.

NOTE: Expansion tanks are pre-charged with a 40 psi air
charge. If the inlet water pressure is higher than 40 psi, the
expansion tank’s air pressure must be adjusted to match
that pressure, but must not be higher than 80 psi.

FIGURE 43.

STRANGE SOUNDS

Possible noises due to expansion and contraction of some metal
parts during periods of heat-up and cool-down do not represent
harmful or dangerous conditions.

Operational Conditions

SMELLY WATER

In each glass-lined water heater there is installed one anode rod
(see parts section) for corrosion protection of the tank. Certain
water conditions will cause a reaction between this rod and the
water. The most common complaint associated with the anode
rod is one of a “rotten egg smell”. This odor is derived from
hydrogen sulfide gas dissolved in the water. The smell is the result
of four factors which must all be present for the odor to develop:

A. A concentration of sulfate in the supply water.

B. Little or no dissolved oxygen in the water.

C. A sulfate reducing bacteria within the water heater. (This

harmless bacteria is non-toxic to humans.)

TROUBLESHOOTING