Architectural and engineering specifications, Technical specifications, Installation of smoke alarm – Kidde 120VAC User Manual

Page 2: Ordering information, Distributed by

Advertising
background image

1394 South Third Street, Mebane NC 27302
1-800-880-6788 • www.kiddeus.com

Architectural and Engineering
Specifications

The smoke alarm shall be Kidde Unit 1285 or approved equal. It shall be powered
by a 120VAC, 60Hz, 80mA source along with a 9V battery back up. The unit shall
incorporate an ionization sensor with nominal sensitivity of 1.26%/ft. The temper-
ature operation range shall be between 40˚F and 100˚F (4˚C and 38˚C) and the
humidity operation range shall be 5% - 95% relative humidity.

The smoke alarm can be installed on any standard single gang electrical box,

up to a 4” octagon junction box. The electrical connection (to the alarm) shall be
made with a plug-in connector. A maximum of 24 Kidde devices can be intercon-
nected in a multiple station arrangement. The interconnect system must not
exceed the NFPA (National Fire Protection Association) limit of 18 initiating devices,
of which 12 can be smoke alarms. With 18 initiation devices (smoke, heat, CO,
etc.), interconnected, it is still possible to interconnect 6 strobe lights and or relay
modules. The unit shall provide optional tamper resistance that deters removal of
the unit from the wall or ceiling.

The alarm shall include a safety light that shall be powered by a 9V alkaline

battery. The safety light shall provide 15 minutes of pulsating light when the alarm
is sounding. The alarm shall include a test button that will electronically simulate
the presence of smoke and cause the unit to go into alarm. This sequence tests
the unit’s electronics, battery and horn to ensure proper operation.

The unit shall include a piezoelectric horn that is rated at 85dB at 10 feet.

The unit shall include the Hush

®

feature that silences the unit. By pressing the

Hush

®

button, it will desensitize the unit for approximately 7 minutes if a nuisance

condition occurs. The alarm will chirp every 30-40 seconds during this time and
will automatically reset after approximately 7 minutes and sound the alarm if parti-
cles of combustion are still present. The Hush

®

feature shall be overridden and the

unit will alarm if the smoke is too dense.

The unit shall also include a low battery warning utilizing a brief alarm chirp

every 30-40 seconds along brief flashed from the safety light for a minimum of
seven (7) days.

The unit shall incorporate one red LED to indicate the alarm’s current status

and mode of operation. The red LED will indicate one of two conditions:
Standby Condition:

The red LED will flash every 30-40 seconds to indicate that
the smoke alarm is operating properly.

Alarm Condition:

When the alarm senses products of combustion and goes
into alarm, the red LED will flash rapidly (one flash per
second). The rapid flashing LED and pulsating alarm will
continue until the air is cleared.

The unit shall incorporate one green LED to indicate the alarm’s current status

and mode of operation. The green LED will indicate one of two conditions:
Standby Condition:

The green LED will be steady on, indication the presence of
AC power.

Alarm Condition:

The green LED of an alarm that senses smoke will flash to
indicate the memory condition. The memory will remain
activated until it is reset by pushing the test button.

The unit shall at a minimum meet the requirements of UL217, NFPA72,

(chapter 11 2002 edition), The State of California Fire Marshall, NFPA 101 (One
and two family dwellings) Federal Housing Authority (FHA), Housing and Urban
Development (HUD). It shall also include a 5-year manufacture’s limited warranty.

120VAC Smoke Alarm
with Exit Light

Unit Number 1285E

Technical Specifications

Unit Number:

1285E

UPC:

0-25417-01285-9

Power Source:

120VAC

Sensor:

Ionization

Audio Alarm:

85dB at 10ft

Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)

Humidity Range:

5% - 95% relative humidity (RH)

Size:

5.6” in diameter x 1.55” depth

Weight:

1lb

Interconnects:

Up to 24 Kidde devices

LED:

Green, receiving ac power
Red, alarm mode

Warranty:

5 year limited

Installation of Smoke Alarm

The combination alarm should be installed to comply with all local codes having
jurisdiction in your area, Article 760 of the National Electric Code, and NFPA 72.
Make certain all alarms are wired to a single, continuous (non-switched) power
line, which is not protected by a ground fault interrupter. A maximum of 1000 ft.
of wire can be used in the interconnect system. Use standard UL listed household
wire (18 gauge or larger as required by local codes).

FUSE OR CIRCUIT BREAKER

BLACK

WHITE

RED

L

N

First
Alarm

Additional
Alarms

Ordering Information

Gift Box UPC: 0-25417-01285-9

**Not for sale by individual unit

MASTER PACK

12

1

UNIT

Part

Dimensions

Case/

Layers/

Skid

Number

I 2 of 5

Pack Quantity

(w x d x h inches)

Weight

Skid

Skid

Weight

1285**

N/A

Individual

5.75 x 1.75 x 5.75

1lb

N/A

N/A

N/A

1285E

200 25417 01258 3

Master Pack (12 units)

5.5 x 11.75 x 11.75

12lbs

84

7

1000lbs

5.6"

1.55"