Voltage requirements

Impedance between neutral and ground wires: less than 2 ohms

Neutral to ground voltage: less than 1 volt AC maximum

Voltage drop across circuit breaker: less than 0.1 volts

Impluse voltage spikes transients: less than 50% of nominal line
voltage

Surge voltage: less than 5’1 of nominal line voltage

AC power quality and
conditioning

In some locations, even though recommended wiring practices have been
followed, the power reaching the scanner may exhibit unstable power
quality characteristics. System errors and intermittent data loss could
result.

Power conditioning equipment may be required to overcome the power
quality problems. Kodak can make arrangements for an on-site power
analysis in an area with exceptionally unstable power.

Consult with your electrical contractor or utility company to ensure that on-
site wiring complies with the specifications and that wall outlets and comply
with codes

Environmental
requirements

This equipment can operate in a typical office environment under the
following conditions:

Scanner

Temperature

Relative

Humidity

Heat

Dissipation

9500/990

59° to 86° F

15° to 30° C

15 to 76%

5200 Btu

Dimensions and
weight

This equipment has the following dimensions and weight, with all optional
accessories included:

Scanner

Height

Width

Depth

Weight

9500

48 in.
122 cm

29 in.
74 cm

51 in.
130 cm

630 lbs
227 kg

990

48 in.
122 cm

29 in.
74 cm

51 in.
130 cm

785 lbs
356 kg