Trouble Shooting Suggestions

Problem

Corrective Suggestion

Wall hook/bracket loose or damaged

Secure, repair or replace

Nozzle obstructed

Clear , clean or replace

Discharge hose assembly worn, cracked

Replace

or damaged.

Hose o-ring missing, cracked or damaged

Replace and lightly lubricate

Hose retainer/band missing or damaged

Replace

Valve discharge port obstructed/dirty

Clean or empty and replace

Pull pin bent, corroded, missing or damaged

Replace

Lever/handle loose, bent or damaged

De-pressurize and replace

Pressure gauge reads outside green area

Check ambient temperature

correlation. De-pressurize and

recharge or replace*

Pressure gauge damaged

De-pressurize and replace*

Gauge operating pressure differs from label

De-pressurize and replace*

Gauge does not indicate for use with dry chemical

De-pressurize and replace*

Gauge does not indicate compatible with

De-pressurize and replace*

valve material

Total charge weight of unit outside tolerance

De-pressurize and recharge

Nameplate instructions missing or illegible

Replace

Agent cylinder damaged or corroded

Inspect and hydrostatic re-test or

dispose of in accordance with

NFPA-10

*For gauge replacement, Kidde recommends the use of Loctite - 242 thread sealant be
utilized and allowed to properly cure.