Operation – Lincoln Electric VANTAGE 575 User Manual

Page 27

Advertising
background image

B-9

OPERATION

B-9

Vantage 575

TABLE B.4 Vantage

Simultaneous Welding and Power Loads

*

Each receptacle is limited to 15 amps.

TABLE B.5 Vantage

Extension Cord Length Recommendations

Current

Voltage

Load

Maximum Allowable Cord Length in m (ft) for Conductor Size

(Amps)

Volts)

(Watts)

2.5

2

mm (14AWG) 4.0

2

mm (12AWG)

6.0

2

mm (10AWG) 10.0

2

mm (8AWG) 16.0

2

mm (6AWG)

25.0

2

mm (4AWG)

15

230

3600

18

(60)

23

(75)

46

(150)

69

(225)

107

(350)

183

(600)

20

230

4800

18

(60)

30

(100)

53

(175)

84

(275)

1373

(450)

Conductor size is based on maximum 2.0% voltage drop

Permissible

Permissible Auxiliary

Welding Output

Power - Watts

Current in Amperes

(Unity Power

Factor

@220 V ±10% *

@ 380 V ±10%

500A-40V

0

0

0

350A/34V

8100

40*

14 amp/phase

200A/30V

12000

50*

18.5 amp/phase

150A/26V

12000

50*

18.5 amp/phase

90A/24V

12000

50*

18.5 amp/phase