Chapter 3: Main Menu and SubMenus

To access the RCM8 Main Menu VIA MODEM:

1. Make sure RCM8 and attached modem are turned on and

properly configured.

2. On the remote PC, set up terminal emulation session for

dial-out access – Connect Using an attached modem, rather
than direct connect to a com port.

3. Once a connection has been established with the RCM8,

press Space Bar to initiate the log-in process.

4. Type the RCM8 password, then press Enter to gain access to

the RCM8. The factory-default password for modem access
is also “RCM8”.

5. From here, continue to Step 3 of the local login process.

Configuration

The Configuration option from the Main Menu lets you view the
current RCM8 settings.

1. Press 1 to display the Configuration menu:

RCM8 V4.0 CONFIGURATION - MON 07-05-99 18:03:20

SITE ID = WEST WING COMPUTER ROOM PAGER ID - 5551149

IN DELAY NO DIAL ALT DIAL MESSAGE

MM:SS NC A CODE B

-------------------------------------------

01 00:00 NO 1 0 0 WATER UNDER FLOOR

02 00:00 NO 1 0 0 HIGH TEMP

03 05:00 NC 2 & 1 DOOR HELD OPEN

04 00:00 NO 0 0 0 CLOGGED FILTER

05 00:00 NO 0 0 0 HIGH HUMIDITY

06 00:00 NO 0 0 0 CONTACT #6

07 00:00 NO 0 0 0 CONTACT #7

08 00:00 NO 0 0 0 CONTACT #8

RCM8 Phone Number =

Phone Number 1 = 9,5551212,,,,,911##

Phone Number 2 = A9,18007596366

Dial Prefix = ATE1X4DT

Redial Tries = 2

Redial Interval = 30

Modem = CONNECTED

Modem Baud Rate = 1200

EIA-485 Online Units =

This is a view-only screen. Use the remaining Main Menu
options to make changes or reset the values shown in this
screen.

2. Press Esc to return to the Main Menu.