Liebert Autochangeover Controllers AC8 User Manual

Product specification/installation sheet, Description, Features and benefits

Advertising
background image

1

AC8

Product Specification/Installation Sheet

Description

The Liebert AC8 is ideal for coordinated control of systems

with redundant equipment, such as multiple environmental

units or pumps. When the AC8 controller detects an alarm in

an operating device, the AC8 enables a standby device and

controls the device in alarm as configured, either leaving that

device operating or disabling it.

The AC8 controller can also balance usage of devices by

rotating units through Operating and Standby modes

according to a user-defined schedule. This helps keep

redundant equipment operating efficiently and only when

needed. The AC8 can perform routine testing of standby

devices and alert personnel if a standby device fails an

operating test and requires attention.

The staging feature permits standby devices to be turned on

or off when a sensor detects specified levels. For example, the

AC8 might be configured to turn on a fan when the

temperature reaches 75°F, then turn on a second fan at 80°F.

When the temperature falls below 80°F, the second fan is turned off; when it drops below 75°F,

the first fan is turned off. Liebert’s TW420 Temperature Transmitter may be connected to any of

the four analog sensor inputs for staging and other functions.

Another capability of the AC8 is monitoring the status of connected devices and keeping

personnel apprised through local alarming. The AC8 employs local alarming and remote paging

services to keep personnel on-site and at remote locations apprised of the status of equipment.

The AC8 controller can interface with

anything that closes an electrical contact.

To improve process efficiency and

troubleshooting, the controller tracks data

in three types of logs: alarm, event and

trend.

The AC8 has both a local LCD interface

and a remote dial-up interface for

configuration and monitoring. Liebert’s

SiteScan Web may also be used for

monitoring, as well as some configuration

functions.

When an alarm condition arises, the AC8

displays alarm information, sounds an

audible alarm, changes the state of the

common alarm relay and turns connected

devices on or off according to user

configuration. If configured, the controller

also sends pager notifications.

For other applications, contact your local

Liebert representative or call

1-800-222-5877.

Features and Benefits

• Custom configuration for specific applications
• Paging capability—up to four pager numbers
• Preconfigured on-board modem
• Alarm, Event and Trend logs with time and

date stamp

• Battery backup to ensure alarm notification
• Backup and download configuration files
• User interface via RS232 or modem connection
• On-board audible alarm
• Configuration data permanently stored in non-

volatile Electrically Erasable Programmable

Read Only Memory (EEPROM) for protection

against power loss

• Real-time clock
• Status LEDs for verification and diagnostics