Available Firing Systems

M9 Hot Surface Ignition with

Electronic Supervision

(Standard)

M7 California Code

Efficiency+

®

Boiler Dimensions & Specifications

Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000

www.Lochinvar.com

FG-5M-3/10-Printed In U.S.A.

EBN-04

Revised EBN-04 9/08)

For Ease In Ordering

By Model Number

E B N

150

This is a 150,000 Btu/hr

natural gas Efficiency+ boiler.

Efficiency+

Boiler

Natural Gas

Input

Standard Features

•

84% AFUE

•

Two Stage Firing

•

Sealed Combustion Chamber

•

Stainless Steel Burners

•

Low NOx Operation Exceeds the most

Stringent Air Quality Requirements

•

ASME Copper Finned Tube Heat Exchanger

•

160 PSI Working Pressure

•

Gasketless Heat Exchanger Design

•

Automatic Reset High Limit

•

Loch-Heat Ceramic Tile Combustion Chamber

•

Hot Surface Ignition

•

ASME Pressure Relief Valve

•

24 Volt Control System

•

Pump Relay

•

10 Year Limited Warranty

on Heat Exchanger
(See warranty for details)

Optional Equipment

•

Adjustable High Limit

w/ Manual Reset

•

Alarm Bell

•

Cupro-Nickel Heat Exchanger

•

Flow Switch

•

Indoor/Outdoor Reset

•

Manual Reset Low Water Cut-Off

w/test

•

MP

2

Sequencer

•

Stack Frame

•

Pump Delay w/ Freeze Protection

Registered Under U.S. Patent #5,989,020

Venting Options

Conventional
Vents into conventional flue or
vent breaching using Type B
double wall vent.

** E+ DirectAire Vent with

Sidewall Inlet
Draws fresh combustion air from
an outside wall horizontally, and
vents combustion by-products
through a vertical flue.

Direct Vent Vertical
Draws fresh combustion
air from outside, and vents
combustion by-products
through a vertical flue.

** Direct Vent Horizontal
Draws fresh combustion air
from outside, then vents
by-products through a side wall.

** Outdoor Vent Kit

Use when indoor space is a
problem or if outdoor location
gives better access.

** Requires factory supplied vent kit.

Efficiency+ Boiler

Dimensions & Spec i fi ca tions

Input

Heating

Net

Model

Max

AFUE Capacity I=B=R

Gas

Vent

Shipping

Number

MBH

%

MBH

MBH

B

D

E

G

Conn.

Size

Weight

EBN150

150

83.2

129

112

19-3/4”

16”

7-1/4”

11-3/4”

3/4”

5”

245

EBN200

200

83.1

170

148

23-3/4”

20”

9-1/4”

11-3/4”

3/4”

5”

265

EBN250

250

83.2

218

190

27-1/2”

23-3/4”

11”

11-3/4”

3/4”

6”

290

EBN300

300

84.0

252

219

31-1/4”

27-1/2”

13”

11-3/4”

3/4”

6”

310

Notes: Change ‘N’ to ‘L’ to denote L.P. gas models

Electrical Requirements: 120 VAC / 2 AMP

Water connections are 1-1/2” NPT

Net ratings based on piping and pick-up allowance of 1.15

Performance data based on manufacturer test results.