Instructions for recessed prospec, Track power feed to track, Instruction sheet no – Lightolier ProSpec IS:26600 User Manual

Page 3: Direct power feed to "feed" track, Feeding along the track length (fig. g)

Advertising
background image

IS:26600

INSTRUCTION SHEET NO.

Instructions for Recessed ProSpec

Track

Power Feed to Track

DIRECT POWER FEED TO "FEED" TRACK

Use solid 12 ga. copper wire when feeding the track. The feed track accepts
two separate 120 V, 60 Hz branch circuits. Each circuit must not exceed the
20 amp capacity of the track system.

FEED FROM ABOVE TRACK (Fig E):

•Remove Bottom cover and save.

•Remove Knockout in Top Plate.

•Remove Top Plate from Track

•Secure electrical connector (by others;

3

/

8

size recommended) to Top

Plate using the Nut provided. Position connector locking screws such
that the screws will be hidden behind the track width.

•Attach Top Plate to track.

•Pass wires through connector and secure the cable or conduit to the

connector.

The track must not support the cable. Use separate support

for securing the cable to the building structure.

•Secure the track to the ceiling (

see mounting on previous page).

•Form the wires in the Feed track to the connector terminals

(see FIG. F). Cut and strip each wire. Attach wires to the screw
terminals. Wires must be tightly held in the screw terminals. Neutral
wires must be attached to screw terminals marked "NEUT”. Ground
wire must be attached to the green ground screw.

•Snap Bottom Cover into the track.

FIG. G

A0397

Page 3 of 4

Electrical

Connector

Knock out

Feed Track

Top Plate

Bottom Cover

FIG. E

Use 12 ga. solid copper wire for feed
connections including ground.

Two wires may be
attached to one
screw terminal.

Circuit 2

Neutral 2

FIG. F

Circuit 1

Neutral 1

.50

Ground Terminal

Power
Terminals

Neutral
Terminals

Wire Cover

Feed End

Floating Splice Box

Dead End

Feed Track Unit

FEEDING ALONG THE TRACK LENGTH (Fig. G)

A floating splice box may be used to feed the "Feed Track" from along the
tracks length. The floating splice box can be mounted anywhere on the track
up to 4' from the end of the track. The wires are passed along the top of the
track and into the feed end of the track. The floating splice box may
only be used when there is accessibility to the splice box after the
installation is complete.
Floating Splice Box (Cat. no. 26660) sold separately. See instructions
supplied with 26660 for complete installation details.