INSTALLATION -

MODEL L20 DVF-2 ONLY

PAGE 10

HORIZONTAL VENT TERMINATION REQUIREMENTS

The venting terminals should not be recessed into a wall or siding.




A = 2” Clearances above grade, veranda, porch, deck or bal-

cony.

B = 12” Clearance to window or door that may be opened.
C = 9” (USA) Clearance to permanently closed window.
12”

(CAN)

D = 24” Vertical clearance to ventilated soffit located above the

terminal within a horizontal distance of 2 feet (60 cm)
from the center-line of the terminal.

E = 12” Clearance to unventilated soffit.
F = 9” Clearance to outside corner.
G = 6” Clearance to inside corner.
H = 3 ft. (USA) Not to be installed above a meter/regulator

assembly within 3 feet (90 cm) horizontally from the
centerline of the regulator.

I =

3 ft. (USA) Clearance to service regulator vent outlet.

6

ft.(CAN)

J = 9” (USA) Clearance to non-mechanical air supply inlet to

building or the combustion air inlet to 12“ (CAN) any
other appliance.

K = 3 ft. (USA) Clearance to a mechanical air supply inlet. 6 ft.

(CAN)

L* = 7 ft. (USA) Clearance above paved side-walk or a paved

driveway located on public property.

M**= 12” Clearance under veranda, porch, deck or balcony

*

A vent shall not terminate directly above a side-walk or paved
driveway which is located between two single family dwell-
ings and serves both dwellings.

** Only permitted if veranda, porch, deck or balcony is fully

open on a minimum of 2 sides beneath the floor.

Note: Local Codes or Regulations may require different clear-

ances.