Table 15 group settings and values, Table 15, Group settings and values – Liebert STS2 User Manual
Page 99
![background image](/manuals/163511/99/background.png)
Communication Interfaces
91
Table 15 shows the various groups, the settings contained within and the type of value it requires.
Table 15
Group settings and values
Group
Item:
Description
Value Type
Value Notes
Group 1:
System
Ratings
1
Input Volts (PDU)
Integer
Set per system spec.
2
Volts
Integer
Set per system spec.
3
Current
Integer
Set per system spec.
4
Frequency
Scaled
Desired freq. x 10 (600 = 60 Hz)
Group 2:
System
Settings
1
Language
Enumeration [Not supported at this time]
2
System Model Number
String
14 Character max.
3
System ID Number
String
8 Character max.
4
System Tag Number
String
8 Character max.
5
System Order Number
String
8 Character max.
6
Options_1
Bitpacked
14 Character max.
7
Autodial Primary Line
String
20 Character max.
8
Autodial Secondary Line
String
20 Character max.
9
Autodial Pager Number
String
20 Character max.
10
Autodial Pager PIN
String
10 Character max.
11
Modem Init String
String
20 Character max.
12
Modem Baud Rate
Enumeration 0 = 2400, 1 = 9600, & 2 = 19200 bps
13
Modem LGS Check - Day
Bitpacked
14
Modem LGS Check - Time
Bitpacked
15
Comms Options 1
Bitpacked
See section 12.1.3.
16
Comms Options 2
Bitpacked
See section 12.1.3.
Group 3:
User
Settings
1
SRC1 Fast Undervoltage Setpoint
Integer
In % of nominal below nominal
2
SRC1 Slow Undervoltage Setpoint
Integer
In % of nominal below nominal
3
SRC1 Slow Undervoltage Detect Delay Integer
In number of lines cycles
4
SRC1 Overvoltage Setpoint
Integer
In % of nominal above nominal
5
SRC1 Overvoltage Detect Delay
Integer
In 1/4 lines cycles
6
SRC1 I peak Transfer Setpoint
Integer
x 10
7
SRC2 Fast Undervoltage Setpoint
Integer
In % of nominal below nominal
8
SRC2 Slow Undervoltage Setpoint
Integer
In % of nominal below nominal
9
SRC2 Slow Undervoltage Detect Delay Integer
In number of lines cycles
10
SRC2 Overvoltage Setpoint
Integer
In % of nominal above nominal
11
SRC2 Overvoltage Detect Delay
Integer
In 1/4 lines cycles
12
SRC2 I peak Transfer Setpoint
Integer
x 10
13
Max. Transfer Phase Angle
Integer
In degrees
14
Output Frequency Deviation
Integer
Freq. in Hz x 10
15
ReTransfer Delay Time
Integer
In seconds
16
Horn Volume
Integer
Range: 1-10
17
Critical Option Enabling
Bitpacked
See section 12.1.3.
18
Non-Critical Option Enabling
Bitpacked
See section 12.1.3.
Group 4:
Event
Mask
Settings
1 to 63
Event Mask settings for faults
Event Mask
See section 12.1.3.
64 to 143 Event Mask settings for alarms
Event Mask
See section 12.1.3.