14.1 System Configuration

The STS2/PDU can be set in several different configurations, according to the model and location. The

configuration is set at the factory and does not need to be changed by the customer.

14.1.1 Frequency

The STS2/PDU accepts input frequencies of 50 Hz or 60 Hz, depending on the model ordered. The fre-

quency shall be within +/- 0.5 Hz of the nominal frequency.

14.1.2 Input Voltage

The STS2/PDU models are available to handle various voltages.
The input voltage must be three phase AC (3 wire-plus-ground).
The voltage shall be within +/- 10% of the nominal voltage.
The following table provides nominal voltages, listed according to frequency.

14.1.3 Output Voltage

The output voltage shall be three phase AC (4 wire-plus-ground).

14.1.4 System Current Ratings

These ratings are based upon continuous switch current rating. All units are 100% continuous cur-

rent rated. Some ratings are not available in certain voltages.

14.1.5 Grounding

Refer to 4.2 - System Grounding for specifications and instructions regarding grounding.

Table 20

Input voltage

60 Hz

(L-L)

50 Hz

(L-L)

208V

208V

380V

380V

400V

400V

415V

415V

480V

-

600V

-

Table 21

Output voltage

60 Hz

(L-L/L-N)

50 Hz

(L-L/L-N)

208/120V

208/120V

380/220V

380/220V

400/230V

400/230V

415/240V

415/240V

Table 22

System current ratings

Current

250A
400A
600A
800A