Table 12 event messages, Table 12, Event messages – Liebert STS2 User Manual

Page 93

Advertising
background image

Alarms and Faults

85

Table 12

Event messages

ID

Alarm Message

Description/Cause

Action

1

S1 SCR SHORT

One or more of the SCRs for Source 1 have shorted and failed.

D, F, A, E

2

S2 SCR SHORT

One or more of the SCRs for Source 2 have shorted and failed.

D, F, A, E

3

S1 SCR OPEN

One or more of the SCRs for Source 1 is open.

D, F, A, E

4

S2 SCR OPEN

One or more of the SCRs for Source 2 is open.

D, F, A, E

5

PRIMARY FAN FAIL

A primary cooling fan has failed and the unit is now being cooled by a

secondary fan, which is not monitored.

D, A, E

6

CONTROL MODULE FAIL

Control logic module has failed.

D, A, E

7

PWR SPLY DC A FAIL

Power supply DC bus A has failed.

D, A, E

8

PWR SPLY DC B FAIL

Power supply DC bus B has failed.

D, A, E

9

PWR SPLY S1 AC FAIL

Power supply Source 1 AC has failed.

D, A, E

10

PWR SPLY S2 AC FAIL

Power supply Source 2 AC has failed.

D, A, E

11

PWR SPLY LOGIC FAIL

A power supply module has failed.

D, A, E

12

OUT VOLT SENSE FAIL

The output volt sense module failed

D, A, E

13

S1 VOLT SENSE FAIL

The Source 1 volt sense module failed.

D, A, E

14

S2 VOLT SENSE FAIL

The Source 2 volt sense module failed.

D, A, E

15

S1 SCR SENSE FAIL

The Source 1 SCR sense module failed.

D, A, E

16

S2 SCR SENSE FAIL

The Source 2 SCR sense module failed.

D, A, E

17

S1 CURR SENSE FAIL

The Source 1 SCR current module failed.

D, A, E

18

S2 CURR SENSE FAIL

The Source 2 SCR current module failed.

D, A, E

19

S1 GATE DRIVE FAIL

The Source 1 gate drive module failed.

D, A, E

20

S2 GATE DRIVE FAIL

The Source 2 gate drive module failed.

D, A, E

21

INTERNAL COMM FAIL

Internal CAN communications failed.

D, A, E

23

CB1 SHUNT TRIP FAIL

CB1 shunt trip failed.

D, A, E

24

CB2 SHUNT TRIP FAIL

CB2 shunt trip failed.

D, A, E

27

EQUIPMENT FAN FAIL

One of the equipment fans failed

D, A, E

28

INPUT 1 SURGE FAIL

Source 1 input surge suppression module failed

D, A, E

29

INPUT 2 SURGE FAIL

Source 2 input surge suppression module failed

D, A, E

64

HEATSINK OVERTEMP

Heatsink has exceeded the recommended temperature.

A, E

65

EQUIPMENT OVERTEMP

Cabinet has exceeded the recommended temperature

A, E

67

S1 UV

Source 1 under voltage, fast detection.

A, E

68

S1 UV (RMS)

Source 1 under voltage, slow detection.

A, E

69

S1 OV

Source 1 over voltage

A, E

70

S1 OF/UF

Source 1 over frequency/under frequency

A, E

71

S1 FAIL

Source 1 failure.

A, E

72

S2 UV

Source 2 under voltage, fast detection.

A, E

73

S2 UV (RMS)

Source 2 under voltage, slow detection.

A, E

74

S2 OV

Source 2 over voltage.

A, E

75

S2 OF/UF

Source 2 over frequency/under frequency.

A, E

76

S2 FAIL

Source 2 failure.

A, E

77

S1 OVERCURRENT

Source 1 over current.

A, E

78

S2 OVERCURRENT

Source 2 over current.

A, E

79

S1 I-PEAK

I-PK on Source 1.

D, F, A, E

80

S2 I-PEAK

I-PK on Source 2.

D, F, A, E

Advertising