Troubleshooting – Lochinvar EnergyRite ER152 User Manual
Page 23
Advertising

Table 3B Inlet/Outlet System Sensor Resistance vs. Temperature
Temperature
Resistance
50
18,780
68
12,263
86
8,194
104
5,592
122
3,893
140
2,760
Checking temperature sensors
The pool heater temperature sensors (inlet and outlet water) are both resistance type devices. The following table shows the
correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a known
temperature. If the resistance of the sensor does not closely match, replace the sensor.
3
Troubleshooting
(continued)
Service Manual
23
Advertising
This manual is related to the following products: