Specifications – Liebert PowerSure PS400-60S User Manual

Page 11

Advertising
background image

11

SPECIFICATIONS

FCC ID #

N/A

BHKAF400T-60

BKAF600T-60

Model # / Stock #

PS250-60/PS250-60S

PS400-60 / PS400-60S

PS600-60 / PS600-60S

Model Rating

250 VA / 150 W

400 VA / 240 W

600 VA / 360 W

Dimensions
Unit (W x D x H)

3.51 x 10.18 x 6.79 in

(90 x 262 x 175 mm)

4.25 x 10.18 x 7.02 in

(109 x 262 x 186 mm)

4.84 x 10.18 x 8.15 in

(124 x 262 x 216 mm)

Shipping (W x D x H)

7.13 x 14.37 x 11.93 in

(181 x 365 x 303 mm)

8.35 x 18.98 x 11.5 in

(212 x 482 x 292 mm)

9.33 x 18.98 x 13.15 in

(237 x 482 x 334 mm)

Weight
Unit

8.8 lb. (4 kg)

12.5 lb. (5.7 kg)

19.8 lb. (9 kg)

Shipping

10.1 lb. (4.6 kg)

15.4 lb. (7 kg)

23.1 lb.(10.5 kg)

AC Parameters
Receptacles

(2) NEMA 5-15

(4) NEMA 5-15

(4) NEMA 5-15

Input Voltage Range

90-135 VAC, Single Phase, 2 Wire Plus Ground

Low Voltage Transfer Point

95 VAC, User Selectable to 90 or 100 VAC

High Voltage Transfer Point

135 VAC

135 VAC, User Selectable to 140 VAC

Input Frequency Range

47 – 53 Hz, 57 – 63 Hz

Output Voltage (on battery)

115 VAC, ± 5%

Output waveform (on battery)

Stepped Sine Wave

Max. Output Current at 120 V

2.1 A

3.3A

5 A

Output Frequency

50 or 60 Hz, ±5%

Max. Overload Capacity

115% of Power Rating

Battery
Type

Sealed, Valve-Regulated Lead Acid, Maintenance-Free

Qty x Voltage x Rating

1 x 12 V x 4.5 AH

1 x 12 V x 7 AH

2 x 12 V x 7 AH

Back-up Time

6 minutes at full load

Time from Low Battery Alarm
to Shutdown

Approximately 2 Minutes, depending on load

Recharge Time

8 – 10 Hours to 90% Capacity

Battery Life

3 – 5 Years Typical

Transfer Time to/from Inverter

2 – 6 msec. Typical

Agency Approvals
Safety

UL, C-UL Listed

EMI / RFI

Meets FCC Part 15, Subpart B, Class B

Surge Protection

Meets IEEE 587, Category A and B

MTBF (Bellcore Method)

100,000 Hours (Excluding Battery)

Environmental Standards
Operating Temperatures

50° F to +104° F (10° C to +40° C)

Storage Temperatures

0° F to +104° F (-20° C to +40° C)

(High Temperatures Reduce Battery Life)

Cooling

Convection

Audible Noise

Less than 40 dB @ 1 meter

Operating Elevation

Up to 9,900 ft. (3,000 m)

Storage Elevation

Up to 33,000 ft. (10,000 m)