Determine water heater location – Lochinvar Shield SNA285-125 User Manual

Page 9

Advertising
background image

OPEN
FRONT

1" MINIMUM CLEARANCE

AROUND HOT WATER

PIPES AND VENT PIPE

Figure 1-2 Alcove Installation - Minimum Required Clearances

1" MINIMUM CLEARANCE

AROUND HOT WATER

PIPES AND VENT PIPE

CLOSED DOOR

VENTILATING
AIR OPENING

VENTILATING
AIR OPENING

*

AREA OF EACH OPENING:

1 SQ. INCH PER 1000 BTU PER HOUR INPUT
WITH A MINIMUM OF 100 SQ. INCHES

6"

6"

Figure 1-1 Closet Installation - Minimum Required Clearances

ƽ WARNING

For closet installations, CPVC
material MUST BE used in a closet
structure due to elevated
temperatures. Failure to follow this
warning could result in fire,
personal injury, or death.

9

1

Determine water heater location

(continued)

RECOMMENDED SERVICE
CLEARANCES:

Top

- 18" (457 mm)

Right Side - 24" (610 mm)
Front -

24" (610 mm)

RECOMMENDED SERVICE
CLEARANCES:

Top

- 18" (457 mm)

Right Side - 24" (610 mm)
Front -

24" (610 mm)

Installation & Service Manual

TM

ƽ WARNING

For alcove installations, CPVC
material MUST BE used in an
alcove structure due to elevated
temperatures. Failure to follow this
warning could result in fire,
personal injury, or death.