Lytecaster performance recessed downlighting – Lightolier 1101 User Manual

Page 3

Advertising
background image

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2010 Philips Group • B1010

Lytecaster Performance Recessed Downlighting

1101

Page 3 of 3

6 ¾" Aperture Vertical Open, Performance Series, Reflector Trim

Job Information

Type:

1101CL HID 100W ED-17 LAMP

1000

2000

3000

1000

2000

3000

60˚

30˚

Coefficients Of Utilization

Ceiling

80%

70%

50%

30%

0

Wall

70 50 30 10 50 10 50 10 50 10

0

RCR

Zonal Cavity Method - Effective Floor Reflectance = 20%

Room Cavity Ratio

0 74 74 74 74 72 72 69 69 66 66 62
1 69 67 66 64 66 63 64 61 61 59 56
2 65 62 59 56 60 55 58 54 57 53 51
3 61 56 52 50 55 49 54 48 52 48 46
4 57 51 47 44 51 44 49 43 48 43 41
5 53 47 43 39 46 39 45 39 44 38 37
6 50 43 39 35 43 35 42 35 41 35 34
7 47 40 35 32 39 32 38 32 38 32 30
8 44 37 32 29 36 29 35 29 35 29 28
9 41 34 30 27 34 27 33 26 32 26 25

10 39 31 27 24 31 24 31 24 30 24 23

Determined In Accordance With Current IES Published Procedures

Luminaire Input Watts =

Candlepower Distribution

Angle

Mean CP

0

2519

5

2547

10

2597

15

2685

20

2747

25

2736

30

2526

35

2135

40

1729

45

1302

50

792

55

284

60

26

65

7

70

4

75

4

80

2

85

2

90

1

Trim/Frame:

1101CL

Lamp lumens:

7900 lm

Input Watts:

119 W

Efficiency:

62.0 %

Spacing Criterion:

1.36

Multiple Unit Data - RCR 2

Spacing

Avg.Initial

Watts/

On Ctr.

Footcandles

Sq. Ft.

6'

121

2.97

8'

84

2.06

10'

54

1.32

38'x38'x10' Room, Workplane 2 1/2'

above floor, 80/50/20% Reflectances

Single Unit Data

Height to

Initial

Beam

Lighted Plane

Footcandles

Diameter

6'

70

8'

8'

39

11'

10'

25

14'

12'

17

16'

Zonal Lumens And Percentages

Zone

Lumens

%Luminaire

0-30

2253

46.0%

0-40

3582

73.0%

0-60

4864

100.0%

0-90

4878

100.0%

CERTIFIED TEST REPORT NO. 4051FR