Lennox International Inc. WING User Manual

Page 20

Advertising
background image

18

To locate the outdoor and the indoor units, refer to the
following information.

L : Distance length between both units.
1 = Refrigerant vapour line.
2 = Liquid aspiration line.

3

4

MODEL

5

2,8

Liquid

Máx.Vertical

Total vertical

+

Horizontal

Tube size

Refrigerant lines sizes

Refrigerant lines sizes L

Max. number of bends

Vapour

15

25

12

15

20

8

15

20

8

15

20

8

3/8"

5/8"(1)

3/8"

3/4"

3/8"(1)

3/4"

1/2"

3/4"

If the height length is greater than 5 meters, a siphon suction must be installed on the suction line every 5 meters
to ensure that oil return to the compressor.
(1) Use the coupling fittings included in indoor unit for refrigerant connection with outdoor unit..

For other positions and longer lengths, consult the Lennox Technical Support Department for application

assistance.

The following data will be obtained from that estimation:

Pipe dimensions, Siphon suction, Insulation, Refrigerant charge

NOTE: THE REFRIGERANT LINES GAS AND LIQUID, MUST BE INSULATED

L

INDOOR UNIT

OUTDOOR U.

2

1

L

INDOOR U.

OUTDOOR U.

L

INDOOR U.

OUTDOOR U.

2

1

1

2

REFRIGERANT CONNECTIONS

DISTANCES BETWEEN UNITS