AUDIBLE ALARM CONDITIONS

CONDITION

ALARM

Battery mode (utility failure)

One short beep every ten seconds

Low battery

Two short beeps every five seconds

Output overload (bypass)

One short beep every half second

Over temperature (bypass)

One second beep every four seconds

DC Bus over voltage (bypass)

One second beep every four seconds

PFC failure (bypass)

One second beep every four seconds

Inverter failure

One second beep every four seconds

Battery Test failure

Two second beep every minute

TROUBLESHOOTING GUIDE

PROBLEM

CAUSE

SOLUTION

UPS is short circuited
or overloaded

Ensure UPS is off. Disconnect
all loads and ensure nothing is
lodged in output terminal block.
Ensure loads are not defective
or shorted internally.

Internal fuse is blown,
indicating internal fault

Do not attempt to open or
service the UPS. Contact your
dealer or technical support.

UPS fails to start when
on button is pressed

Breaker not closed or
has tripped.

Close breaker or remove
overload.

UPS input not
connected

UPS is operating from battery
mode, make certain UPS is
securely connected to source.

UPS input protection
has opened

UPS is operating from battery
mode. Save data and close
applications. Replace UPS
input fuse or reset input
breaker, then restart UPS.

Battery indicator is
illuminated

Mains voltage out of
UPS input range.

UPS is operating from battery
mode. Save data and close
applications. Ensure mains
supply voltage is within
acceptable limits for UPS.

Batteries not fully
charged

Apply input voltage for at least
24 hrs to recharge batteries.

UPS is overloaded

Check load level display and
reduce load level

UPS has reduced
battery time

Batteries may not be
able to hold a full
charge due to age

Replace batteries. Contact
your dealer or technical
support.