Installation

2

2.0

I

NSTALLATION

2.1

Liebert NX UPS to Liebert NX UPS

1. Connect the power cables of the adapter to the Phase A, Neutral and Ground output of each UPS.
2. Connect the LBS cable to COM1 of each LBS Signal Adapter.
3. Connect the other end of each LBS cable to X4 on the parallel board (UHW241M3) in the

NX UPS.

4. Connect the communication cable (up to 492 ft. [150m]) to the COM2 interface of each LBS Signal

Adapter.

5. The switch of both LBS signal adapters should be in the right position (see Figure 4).

Figure 4

Connecting a Liebert NX to a Liebert NX

!

WARNING

Installation by qualified electrical personnel only—hazardous voltage may be present at the

UPS output connectors.

COM1

COM1

COM2

COM2

SWITCH

SWITCH

Power ON

LED1

Power ON

LED1

Power Cable

Connect to NX UPS

LBS

Cable

Communication Cable

up to 492 ft. (150m)

Power Cable

Connect to NX UPS

LBS

Cable