Lennox Hearth CR-3835R User Manual

Page 20

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

20

FINISH TO YOUR TASTE

There are a wide variety of “finished looks” for
these fireplaces, from formal wall decor with
elaborate mantels to rustic wood paneling or
warm brick facings.

Only noncombustible materials like stone, tile,
brick, etc., may overlap the black front facing.
Do not extend these materials beyond the black
facing and into the firebox area. Be sure not to
interfere with the installation and operation of
glass doors or block the upper or lower grilles.
Seal all joints between the black facing and wall
surrounds to prevent air intrusion. Use non-
combustible caulking material only to seal the
black metal facing to the surround material on
the finished wall.

Combustible materials may project beyond the
sides of the fireplace opening as long as they
are kept within the shaded areas illustrated in
Figure 46.

Model

Part Number

Weight

CR-3835R

P/N 015014

210 lbs.

CR-3835L

P/N 015013

210 lbs.

12"

Min. Distance To

Unprotected Side Wall

8"

45

°

Combustible

Materials

Allowed In

Shaded Area

“Safe Zone”

8"

Min. Distance To

Protected Side Wall

Fireplace

11

⁷⁄₈”

15

⁷⁄₈”

Figure 46

Figure 45

Secure the hearth extension to the floor to
prevent possible shifting.

6"

Max. Thickness Of Hearth Extension

When Models Are On The Floor

Figure 44

20"

(508mm)

Inside Corner

If Less Than 12"
(305mm) Wall
Shield Required

20"

(508mm)

40"

(1016mm)

Wall

Shield

40"

(1016mm)

Metal Safety

Strip

Wall Shield

Not Required

On This Wall

WARNING: THE CRACK BETWEEN THE
FIREPLACE AND THE HEARTH EXTEN-
SION MUST BE SEALED WITH A NON-
COMBUSTIBLE MATERIAL.

Calculating Minimum Thickness if Multiple
Materials are Used

At times it is important to know what
combination of materials are acceptable for
use as floor protection. The “R values” are
used to determine acceptable combinations of
materials because “R values” are additive where
r and k values are not.

“R value” = 1/k = “r” x thickness of material
used

Example: Given that the required “R value”
for a suitable floor protector used must be
equal to or greater than:

“R” = r

L

x T

L

= 1.19 x 1” = 1.19.”

If it is desired to elevate a marble hearth ex-
tension to a level of 5” or more above the floor
surface. What combination of noncombus-
tible materials can be used to accomplish this?

If common brick is used so that the 3 1/2”
dimension is the height, “R” for the common
brick becomes:

brick

“R”

M

= r

M

x T

S

= 0.20 x 3 1/2" = .70

Using 1/2” of mortar to set the brick, “R” for
the mortar is calculated as follows:

mortar

“R”

M

= r

M

x T

S

= 0.20 x 1/2" = .10

Next, a 3/4" marble slab set in 1/2" mortar cov-
ers the brick, “R” for the marble and mortar
becomes:

marble

“R”

M

= r

M

x T

S

= 0.05 x 3/4" = .038

mortar

“R”

M

= r

M

x T

S

= 0.20 x 1/2" = .10

The sum of all “R values” is: .70 + .10 +. 038
+ .10 = .938

This would NOT be an acceptable combination
of material for the hearth extension since the
total calculated “R value” of the materials used
is under the required “R value” of 1.19. An
additional layer of insulating materials must
be used.

Note: Also see NFI Certification Manuals for
expanded explanation on calculating “R val-
ues” when multiple materials are used.

WARNING: WHEN INSTALLING HEARTH
EXTENSION IN FRONT OF A NON-CIRCU-
LATING FIREPLACE MODEL, THE FIRE-
PLACE MUST BE RAISED IF HEIGHT OF
HEARTH EXTENSION EXCEEDS 7" ABOVE
THE BOTTOM OF FIREPLACE (

FIGURE 45 ).