Operating information, Status display screens – Lochinvar COPPER-FINN2 502 User Manual

Page 55

Advertising
background image

55

Installation & Operation Manual

7

Operating information

(continued)

Status Display Screens

By using the Previous/Next (, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the 11 display
screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they
can display:

Screen #

Display Shows

Description

Screen #1

Line 1

HTR: OFF

The unit has been turned OFF by the Enter/Reset button on the
SMART SYSTEM display panel.

HTR: STAND-BY

The unit’s water temperature set point has been met and there is
no call for heat demand being received from either the external
thermostat or the BMS.

HTR: SETPOINT MET

The unit’s water temperature set point has been met, but is still
receiving a call for heat from either a remote thermostat or a BMS.

HTR: PRE-PURGE

The unit has initiated the combustion air purge cycle upon a call for
heat.

HTR: IGNITER * ON

The unit has begun the igniter heatup cycle prior to the trial for
ignition. Display will show IGNITER A or IGNITER B depending on
which stage has priority.

HTR: RUN STG ****

The unit has fired and is running at the displayed number of stages
(1,2,3,4).

HTR: POST-PURGE

The call for heat has been satisfied and the unit runs the fan to clear
the combustion chamber and vent system of residual flue products.

HTR: SERVICE MODE

The unit has been placed in a temporary mode that will allow the unit
to fire for the purpose of combustion analysis.

Screen #1

Line 2

OUT: ***F

The outlet temperature is displayed by the control.

OUT: OPEN

The control does not detect the outlet sensor.

OUT: SHORTED

The outlet sensor wires or the sensor itself has become shorted.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #2.

Screen #2

Line 1

INLET: ***F

The inlet temperature is displayed by the control.

INLET: OPEN

The control does not detect the inlet sensor.

INLET: SHORTED

The inlet sensor wires or the sensor itself has become shorted.

Screen #2

Line 2

RISE: ***F

The difference between the inlet temperature and the outlet temperature
is displayed.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #3.

Screen #3

Line 1

SYSSUP: ***F

The system supply temperature is displayed by the control.

SYSSUP: OPEN

The control does not detect the system supply sensor.

SYSSUP: SHORTED

The system supply sensor wires or the sensor itself has become shorted.

Status display screens