Framing, Facing And Mantel

The construction of the framing, facing, and

mantel must be in accordance with the stan-

dards and the following illustrations (Figures

7a, 7b and 8):

A. Frame the fireplace using 2” x 3” or heavier

lumber.

B. WARNING: Combustible materials

cannot be used in the space directly

above the fireplace, except for the

studs above the facade that support

the facing and mantel. This area must

remain empty for a height of 6’8”

(2,032 mm) measured from the base

of the appliance.

C. Frame the fireplace with vertical studs at the

sides of the fireplace running from floor to

ceiling (see Figure 8). If combustible facing

is to be used, position the studs back, from

the front edge of the fireplace (a space that

is the thickness of the facing material, so

that the facing can be installed flush with the

fireplace facing). Frame headers between

the vertical studs only as follows:

- Place 2” x 3” or 2” x 4” headers,

only along the upper part of the front,

side and back faces (some codes

may require a 2” x 6 ” on an outside

bearing wall). Do not put wood or any

combustible material within the area

above the fireplace except on the front

facing.

- Place headers only as required to support

the facing and mantel.

D. WARNING: The fireplace must not be

in contact with any insulation or loose

filling material. Cover the insula-

tion with Drywall panels around the

fireplace.

Hearth Extension Requirements

The Brentwood fireplace may be installed

directly on a combustible floor. The supplied

safety metal strip must be positioned as fol-

lows: One half under the front of the fireplace

and the other half must extend on the floor

over which the hearth extension will be built

(see Figure 7a).

* The safety metal strip must cover the entire

width of the fireplace

The combustible floor in front of the fireplace

must be covered with a non-combustible

material (tile, marble, stone, etc). See Figures

7a and 7b.

COLD CLIMATE INSTALLATIONS

Climates where temperatures will fall below

32° F (0° C).
The heating performance of the appliance will

vary depending upon the level of insulation,

house design, how the appliance is operated,

etc.
If this fireplace is being installed in a cold

climate, it is especially important to seal all

cracks around the fireplace and wherever cold

air could enter the room with noncombustible

material.

Figure 7b - Hearth Extension Requirements

Area where wood

Mantel can be

installed

Non-Combustible Material

45 Deg.

18”

36”

4”

17” Min.

Also, the outside air inlet duct should be wrapped with noncombustible insulation to minimize

the formation of condensation. Do not place insulation materials directly against the chimney

sections. We recommend that you use the insulated wall radiation shield since it will maintain

the home’s thermal barrier. AC chimney is NOT recommended in very cold climates (in areas with

temperatures below 0° F (-18° C).

(102mm)

(914mm)

(432mm)

(457mm)

45”

(1143mm)

Min.

Hearth

Extension

Mantel

8

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

WARNING: THE HEARTH EXTEN-
SION IS TO BE INSTALLED ONLY
AS ILLUSTRATED.

The crack between the fireplace

and the hearth extension must be

sealed with a non-combustible

material such as sand-cement

grout.

Safety Metal Strip

Hearth Extension

Non-Combustible

Finish Material

Floor

Figure 7A - Hearth Extension Requirements

Fireplace

1/2”

13mm

u

Elevated fireplace installations

require a special “Z” Metal

Safety Strips (field provided),

in place of the safety metal strip

shown above. The safety strip

should extend the full width of

the fireplace. When more than

one safety strip is used they must

overlap by a minimum of 1”.

Platform

2”

Fireplace

Elevated Fireplaces