Water connections – Lochinvar COPPER-FIN 497 - 2067 User Manual
Page 34
Advertising

34
1" TEMPERATURE
AND PRESSURE
GAUGE
AUTOMATIC AIR
ELIMINATOR/VENT
SYSTEM
OUTLET
SYSTEM
SENSOR
LOCATION
SYSTEM
INLET
BUFFER
TANK
DRAIN
PUMP
COMMOM MANIFOLD
MUST BE SIZED TO
ACCOMMODATE COMBINED
FLOW RATE FOR
ALL BOILERS
Figure 4-8_Primary/secondary piping with buffer tank
*Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
NOTICE
Installation & Service Manual
4
Water connections
COMMON MANIFOLD SIZE (Min.)
Models: 497 - 747
Number of Units
GPM
Diameter
(in.)
2
120
3 1/2
3
180
4
4
240
5
5
300
5
6
360
6
7
420
6
8
480
6
COMMON MANIFOLD SIZE (Min.)
Models: 987 - 2067
Number of Units
GPM
Diameter
(in.)
2
180
4
3
270
5
4
360
6
5
450
6
6
540
6
7
630
8
8
720
8