Job Information

Type:

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2009 Philips Group • C0609

Architectural Decorative

4R35

Page 2 of 2

Pendalux Traditional 35" Diameter Body 6-26/32/42 Triple Tube

ANGLE MEAN CP LUMENS

0

495

5

497

47

10

490

15

480

136

20

468

25

450

208

30

430

35

404

253

40

373

45

340

263

50

304

55

268

240

60

231

65

190

190

70

154

75

118

126

80

85

85

56

68

90

44

CERTIFIED TEST REPORT NO. 4R35642A

COMPUTED BY LSI PROGRAM **TEST-LITE**

LIGHTOLIER INDIRECT/DIRECT PENDANT FIXTURE

CAT. #4R35642SNU, 35” DIFFUSER

6-42W T/E SYLVANIA LAMPS. LUMEN RATING = 3200 LMS.

3-ADVANCE BALLAST #ICF-2S42-M2-LD, 120 VAC

TESTED ACCORDING TO IES PROCEDURES. TEST DISTANCE EXCEEDS FIVE

TIMES THE GREATEST LUMINOUS OPENING OF LUMINAIRE.

ANGLE MEAN CP LUMENS

90

44

95

235

347

100

757

105

1311

1339

110

1681

115

1932

1913

120

2163

125

2341

2083

130

2442

135

2546

1973

140

2654

145

2727

1707

150

2764

155

2785

1290

160

2818

165

2679

750

170

2401

175

2363

231

180

2540

C

ANDLEPOWER SUMMARY

DATE: MAR. 1, 2001
PREPARED FOR:
LIGHTOLIER, FALL RIVER, MA

ZONAL LUMENS AND PERCENTAGES

ZONE

LUMENS % LAMP %LUMINAIRE

0-30

424

2.22

3.23

0-40

699

3.64

5.31

0-60

1246

6.48

9.47

0-90

1659

8.64

12.62

40-90

1069

5.01

7.31

60-90

414

2.16

3.15

90-180

12631

65.79

95.98

0-180

14269

74.43

100.00

** EFFICIENCY = 74.4% **

COEFFICIENTS OF UTILIZATION ZONAL CAVITY METHOD

%EFFECTIVE FLOOR CAVITY REFLECTANCE = .20

80

70

50

30

10

50 30 10 50 30 10 50 30 10 50 30 10 50 30 10 0

1

.58 .55 .53 .51 .49 .46 .37 .36 .35 .24 .24 .23 .13 .12 .12 .08

2

.51 .47 .43 .44 .41 .38 .32 .30 .28 .21 .20 .19 .11 .10 .10 .07

3

.45 .40 .36 .35 .35 .32 .29 .26 .24 .19 .17 .16 .10 .09 .09 .06

4

.39 .34 .31 .34 .30 .27 .25 .22 .20 .17 .15 .14 .09 .08 .07 .05

5

.34 .30 .26 .31 .26 .23 .22 .20 .17 .15 .13 .12 .08 .07 .06 .04

6

.31 .26 .22 .27 .23 .20 .20 .17 .15 .13 .12 .10 .07 .06 .06 .04

7

.28 .23 .19 .24 .20 .17 .18 .15 .13 .12 .10 .09 .06 .05 .05 .03

8

.25 .20 .17 .22 .18 .15 .16 .13 .11 .11 .09 .08 .06 .05 .04 .03

9

.22 .18 .14 .20 .16 .13 .15 .12 .10 .10 .08 .07 .05 .04 .04 .02

10

.20 .16 .13 .18 .14 .11 .13 .11 .09 .09 .07 .06 .05 .04 .03 .02

DETERMINED IN ACCORDANCE WITH CURRENT IES PUBLISHED PROCEDURES

Features

1. Diffusing Reflector: White translucent acrylic, 3/16” thick.
2. Inner Dirt Shield: White translucent acrylic, 1/8” thick.
3. Chassis: Steel 20 gauge, semi-gloss white powder-coat finish.
4. Suspension: Swivel (central) stem, 5/8” steel tube. Canopy, steel, 7” Dia.

fastened internally, no exposed hardware. Permits installation on ceilings
with slope of up to 45°. Complies with California Code.

5. Rods: Reflector Bowl is suspended from a central point on three 3/16” steel

rods.

6. Lampholder: Multi-wattage, 4-pin, will accept either GX24q-3 or GX24q-4

lamp base.

7. Flange Trim: Steel 20 gauge, Plated or Painted finish.

Lamping (by others)

Compact Fluorescent: Triple Tube, 26, 32, or 42 Watts.

General Electric

Osram/Sylvania

Philips

26W Triple Tube 4-Pin

(Amalgam) Compact

Fluorescent Lamp

F26TBX/*/A/4P

CF26DT/E/IN/*

PL-T26W/*/4P

32W Triple Tube 4-Pin

(Amalgam) Compact

Fluorescent Lamp

F32TBX/*/A/4P

CF32DT/E/IN/*

PL-T32W/*/4P

42W Triple Tube 4-Pin

(Amalgam) Compact

Fluorescent Lamp

F42QBK/*/A/4P

CF42DT/E/IN/*

PL-T42W/*/4P

*Manufacturers’ color temperature designation.

Electrical

Ballast: Electronic, 2-Lamp HPF, Class P, Programmed Start. Universal Voltage
120/277V, Multi-Wattage 26/32/42W.
6 Lamp

26 Watt

32Watt

42Watt

Voltage

120V 277V

120V 277V 120V 277V

Total Input Watts

168

168

210

210

279

279

Max. Line Current(amps)

2.22 0.96

1.40

2.80

1.20

1.60

Power Factor

>0.98 >0.98

>0.98 >0.98 >0.99 >0.99

Ballast Factor

1.02 1.02

0.96

0.96 0.95 0.95

THD <10% Minimum Starting Temperature: -5˚F/-20˚C

Mounting

Mounts directly to 4” outlet box, using crossbar hanger, supplied.

Labels

cULus Suitable for Damp Locations.

Application Data

35 Inch Diameter

36’ x 36’ x 11’ Space
Luminaire

Spacing: 12’ x 12’

Susp. Dist. 35”

2 Lamps

26W

32W

42W

TTT

TTT

TTT

Illum. (FC) Maint.

28

37

49

Lum.Ratio

8/1

8/1

8/1

Watts/Sq. Ft.

1.15

1.42

1.94

Reflectancies: 80% Ceiling, 50% Walls, 20% Floor.
Light Loss Factor = .75 (.88 BF x .85)
FC (footcandles) at 30” work plane.