INSTALLER settings (continued)

ENERGY EFFICIENT RECOVERY
When turned on, the thermostat will look up to two hours before the next event and anticipate when
to turn on to reach the desired temperature.
NOTE: This will not allow the second stage to turn on until 20 minutes before the event.

DEADBAND SETPOINT
Deadband is used only when the AUTO CHANGEOVER feature is enabled. The deadband is the
temperature difference between the heating and cooling setpoints. This is adjustable from 3-8°F
(2.0-4°C).

HUMIDITROL
If the HUMIDITROL accessory is present in the HVAC equipment, this feature should be enabled.
Otherwise, it should be disabled.

SECURITY CODE
Enter a code to prevent changes to the INSTALLER settings.

23

USER MENU

SELECT

ENTER SECURITY CODE

FOR INSTALLER

SETTINGS

0

0 0 0

USER MENU

SELECT

ENERGY EFFICIENT

RECOVERY

DISABLE

ENABLE

USER MENU

SELECT

DEADBAND SETPOINT

3

˚F

INSTALL MENU

SELECT

HUMIDITROL

DISABLE

ENABLE

110-1052F 5/12/05 11:59 AM Page 23