Troubleshooting, Checking temperature sensors – Lochinvar ARMOR 150 - 800 User Manual
Page 23

3
Troubleshooting
Service Manual
23
3
Troubleshooting
(continued)
Table 3B - Inlet/Outlet System Sensor Resistance vs. Temperature
Temperature °F
Resistance
Ω
Temperature °F
Resistance
Ω
50
18,780
158
1,990
68
12,263
176
1,458
86
8,194
194
1,084
104
5,592
212
817
122
3,893
--
--
140
2,760
--
--
Table 3C - Flue Temperature Sensor Resistance vs. Temperature
Temperature °F
Resistance
Ω
Temperature °F
Resistance
Ω
68
14,773
176
1,707
86
9,804
194
1,266
104
6,652
212
952
122
4,607
230
726
140
3,252
248
560
158
2,337
--
--
Checking temperature sensors
The water heater temperature sensors (inlet water, outlet water, system water, and flue) are all resistance type devices. The
following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the
sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor.