LG 395CAV User Manual

Page 7

Advertising
background image

WARNING:

Use the proper length of pipes to avoid

stress on the gas control manifold. Failure to follow this
warning can result in a gas leak, causing fire, explosion,
personal injury, or death.

CAUTION:

Connect the gas pipe to the furnace using a

backup wrench to avoid damaging gas controls.

WARNING:

Never purge a line into a combustion

chamber. Never use matches, candles, flame, or other
sources of ignition for the purpose of checking leakage.
Use a soap-and-water solution to check for leakage.
Failure to follow this warning can cause a fire, explosion,
personal injury, or death.

VI.

ELECTRICAL CONNECTIONS

A.

115-v Wiring

Refer to the unit rating plate or Table 5 for equipment electrical
requirements. The control system requires an earth ground for
proper operation.

CAUTION:

Do not connect aluminum wire between

disconnect switch and furnace. Use only copper wire.

Make all electrical connections in accordance with the National
Electrical Code (NEC) ANSI/NFPA 70-1996 and local codes or
ordinances that might apply. For Canadian installations, all elec-
trical connections must be made in accordance with CSA C22.1
Canadian Electrical Code, or authorities having jurisdiction.

WARNING:

The cabinet MUST have an uninterrupted

or unbroken ground according to NEC, ANSI/NFPA
70-1996 and Canadian Electrical Code, CSA C22.1 or
local codes to minimize personal injury if an electrical
fault should occur. This may consist of electrical wire or
conduit approved for electrical ground when installed in
accordance with existing electrical codes. Do not use gas
piping as an electrical ground. Failure to follow this
warning could result in electrical shock, fire, or death.

The auxiliary junction box (J-box) can be moved to the left-hand
side of the furnace when a left-side power supply is desired.
Remove the 2 screws holding the auxiliary J-box. Mount the J-box
on the left-hand side of the furnace (holes have been pre-drilled in
casing). When moved, tuck the wiring harness behind the clip
provided to keep extra wire lengths out of the way.

NOTE:

Proper polarity must be maintained for 115-v wiring. If

polarity is incorrect, control board fault code indicator light will
flash rapidly and the furnace will not operate.

B.

24-v Wiring

Make field 24-v connections at the 24-v terminal strip. (See Fig.
9.) Connect terminal Y as shown in Fig. 8 for proper cooling
operation. Use only AWG No. 18, color-coded, copper thermostat
wire.

The 24-v circuit contains an automotive-type, 3-amp fuse located
on the main control board. Any direct shorts during installation,
service, or maintenance could cause this fuse to blow. If fuse
replacement is required, use ONLY a 3-amp fuse of identical size.

C.

Accessories

1. Electronic Air Cleaner (EAC)

Two spring clamp terminals (for 12 gage maximum, solid
or stranded wire), marked EAC-1 and EAC-2 are provided
for EAC connection. (See Fig. 9.) These terminals are
energized with 115-v, (1-amp maximum) during blower
motor operation. To connect EAC power leads to furnace
control center, strip approximately 1/8 in. of insulation from
wire. Open terminal by depressing switch arm with a
screwdriver or finger, and insert wire as shown in Fig. 10.

2. Humidifier (HUM)

Screw terminals (HUM and Com) are provided for 24-v
humidifier connection. The terminals are energized with
24-v 0.5-amp maximum after inducer motor prepurge
period.

NOTE:

A field-supplied, 115-v controlled relay connected to

EAC terminals may be added if humidifier operation is desired
during blower operation.

VII.

VENTING

Refer to the National or Local Installation Code such as; National
Fuel Gas Code Z223.1-1992, or the Canadian Installation Code,
CAN B149.1- and .2-M95, for proper vent sizing and installation
requirements. Use the enclosed Venting Tables for Category I
Fan-Assisted Furnaces for a quick, easy reference. The horizontal
portion of the venting system shall maintain a minimum of 1/4-in.
upward slope per linear ft and it shall be rigidly supported every 5
ft or less with hangers or straps to ensure that there will be no
movement after installation.

VIII.

START-UP, ADJUSTMENT, AND SAFETY CHECK

A.

General

NOTE:

Proper polarity must be maintained for 115-v wiring. If

polarity is incorrect, control board fault indicator light will flash
rapidly and furnace will not operate.

Fig. 7—Typical Gas Pipe Arrangement

A89417

GAS

SUPPLY

MANUAL
SHUTOFF
VALVE
(REQUIRED)

SEDIMENT
TRAP

UNION

—7—

Advertising