Specifi cations – LST Extinguishing Control Panel BC06-1EXT User Manual

Page 4

Advertising
background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

BC06EXT_DBL_LST_EN_0826.PDF • PAGE 4

A

Building Safety. Building Security.

Specifi cations

Mains voltage

230VAC +10/-20%, 47...63Hz

Output/nominal voltage

typ. 27.6VDC

Output current

max. 2.2A

Output current siren outputs

output 1

max. 1A

output 2

max. 0.5A

(the sum of the currents of the signalling devices that are connected to the two outputs must not exceed 1A!)

Output current, extinguishing output

max. 1A

Output current, activated condition output/signal output

max. 500mA per output

Own current consumption (incl. extinguishing board) at 24V

typ. 80mA (without optional componentries, line termination 5.6kΩ)

typ. 65mA (without optional componentries, line termination 47µF)

Line voltage

typ. 20V (line termination 5.6kΩ)

typ. 23V (line termination 47µF)

Line current without fi re detectors

typ. 3.7mA (line termination 5.6kΩ)

typ. 0mA (line termination 47µF)

Line termination

5.6kΩ or 47µF

Line resistance

max. 50Ω per core

Ambient temperature

-5°C to +50°C

Relative humidity

max. 95% (no condensation)

Dimensions W × H × D

330 Ч 330 Ч 90 (mm)

Colour

grey-white, RAL 9002

Weight without batteries

approx. 3kg

Approvals

0786-CPD-20300

VdS pending

Fire Detection Control Panel BC06-1EXT

Order number

210223

Order name

Fire Detection Control Panel BC06-1EXT/INT1

Fire Detection Control Panel BC06-2EXT

Order number

210224

Order name

Fire Detection Control Panel BC06-2EXT/INT1

Functions of EN 12094-1

All mandatory functions of EN 12094-1 are integrated

into the Fire/Extinguishing Control Panels BC06-1EXT

and BC06-2EXT. Furthermore, the most important opti-

onal functions of this standard are supported:

• Parameterisable pre-discharge-warning time for the

delay of the activation

• Detector zone „extinguishing medium active“ se-

lectable for detecting the fl ow of the extinguishing

medium

• Monitoring of components of the extinguishing sys-

tem

• Input for connection of an emergency hold device

• Monitoring of a disable device

• Parameterisable fl ooding time

• Possibility to switch to the „manual only mode“

• Transmission of the triggering signal to further actu-

ations within the extinguishing system – for example,

warning devices

• Transmission of the triggering signal to further actua-

tions outside the extinguishing system – for example,

for turning off the air conditioning system

• Emergency abort device can be connected

• Activation of alarming devices with different alarm

signals