NOTE: DIAGRAMS AND ILLUSTRATIONS ARE NOT TO SCALE

Vertical Cap

Termination

Connector

Exhaust

Intake

Combustion Air Intake

Venting Requirements

Approved Vent Systems:

Lennox Hearth Products Co-linear Chimney Liner Kit Recommended:

• The Flex Kit, Cat. No. H0909 includes one 35 feet flex liner and four

gear clamps.

• The Termination Kit, Cat. No. TKDVI includes the termination cap with two

co-linear collars for 3 inches (76 mm) flex attachments and flashing.

Secure Vent™ Co-Linear Chimney Liner Kit Recommended:

• Direct Vent Vertical Termination Kit (includes Vertical Termination

Cap gas/Connector, Flashing, Qty 2 of 25 feet (7.6 M) length of 3 inches

(76 mm) Aluminum Flex, Clamps and Sealant) #DV3FK25

• Direct Vent Vertical Termination Kit (includes Vertical Termination Cap/

Connector, Flashing, Qty 2 of 35 feet length of 3 inches Aluminum

Flex, Clamps and Sealant) #DV3FK35

Standard Simpson Dura-vent Co-linear Chimney Liner Kit recom-

mended:

• Direct Vent Vertical Termination Cap #991

• Liner Termination Kit

(includes termination connector and flashing) #923GK

• 3" x 35 feet (76 mm x .91 M) Alum Flex #2280

Selkirk/Metalbestos Direct-Temp Co-Linear Chimney Liner Kit recom-

mended

• Direct Vent Vertical Termination Cap #4DT-VC

• Liner Termination Kit

(includes termination connector and flashing) #4DT-CTB

• 3” x 35’ (76 mm x .91 M) Aluminum Flex #AF3-35L

Amerivent Direct Co-Linear Chimney Liner Kit recommended

• Direct Vent Vertical Termination Cap #4DVC

• Co-Linear Adaptor #4DCAT33

• Flashing #4DF or #5DF

• 3” x 35’ Aluminum Flex #3AFL-35

The existing fireplace chimneys may take

various contours which the flexible liners will

accommodate. However, keep the flexible liner

as STRAIGHT as possible, avoid unnecessary

bending.

Liner Requirements:

Vertical Height Min. = 10 ft. (3.05 M)

Vertical height Max. = 35 ft. (10.67 M)

Use 3" (76 mm) diameter listed gas

vent liner (UL1777 ONLY) for the

EXHAUST

Use 3" (76 mm) diameter listed

liner (UL 181 or UL1777) for the

AIR INTAKE.

The flexible vent pipe

must NOT be allowed to

sag behind insert or in

fireplace flue.

The standard cap

in Termination Kit,

TKDVI, is a high

wind cap

Make sure that both liners will pass through existing damper area. Remove

or lock damper to allow the passage of the flexible liners. If the damper

will not allow the passage of both liners, DO NOT PROCEED FURTHER.

(If fireplace is masonry) Consult a local mason for removal of the damper

without risk of structural damage or leakage (if the fireplace is factory

built) The appliance may NOT be installed into the fireplace.

Figure 6b

WARNING

Do not substitute the heat-rated flex liner (UL1777) for the

exhaust with any other type liner or a fire may result caus-

ing property damage, personal injury or loss of life.

Positive Flue Connection (acceptable methods for sealing chimney throat)

Masonry and Factory Built Fireplaces

A qualified installer should evaluate the existing fireplace to determine the

best method for achieving a positive flue connection between the vent and

intake liners and the chimney. One method is to secure a noncombus-

tible seal-off plate (i.e. 22-gage sheet steel) in the fireplace throat using

masonry screws. Other acceptable methods include packing unfaced

fiberglass insulation around the liners. Whichever “seal off” method is

used must effectively seal the area to prevent room air passage to the

chimney of the fireplace.

Air Inlet Liner (for combustion air) When

terminating the air inlet liner at this point, a

positive flue connection is required (to ensure

combustion air is drawn down the chimney

only).

Exhaust 3" (75mm) UL

1777. A full length liner

is required from the

exhaust outlet on appli-

ance to center collar of

termination cap.

Positive Flue Con-

nection (sealing

fireplace throat

using a noncombus-

tible seal-off plate

or insulation).

The outside air inlet does not

require a full reline (if intake

liner is terminated in chimney

and a positive flue connection

is achieved as specified).

Ai

r I

nl

et

Ex

ha

us

t

Ai

r I

nl

et

Existing Fireplace Flue

(chimney)

Masonry and Factory Built Fireplaces

Figure 6a - Terminating Air Inlet in Chimney