2 monitor/mimic display screen, Figure 7 monitor/mimic display screen, Input metering displays – Liebert 610 User Manual

Page 29: Output metering displays, Monitor/mimic display screen, Figure 7

Advertising
background image

Operation

23

3.2.2 Monitor/Mimic Display Screen

From Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the Select

pad and the Monitor/Mimic screen is displayed.

Figure 7

Monitor/Mimic display screen

The Monitor/Mimic display screen is a simplified block diagram of the UPS system. This screen gives

the operator an overall view of the power flow through the UPS system. The screen consists of three

major sections: the input/UPS metering section, the load metering section and the status and alarm

message areas. The metered parameter values on the Monitor/Mimic screen are updated at one-sec-

ond intervals.

Input Metering Displays

Item 1 - Bypass Input: This block displays the bypass input voltage and the bypass input frequency.

The bypass circuit breaker is shown to the right of this block. The status of the circuit breaker is illus-

trated as open or closed.
Item 2 - UPS Input Pwr: This block displays the UPS input voltage and current. The input circuit

breaker is shown to the right of this block. The status of the circuit breaker is illustrated as open or

closed.
Item 3 - Battery Block: This block displays the DC bus voltage and the charge or discharge current

to or from the battery. This block reads MODULE DC BUS when the battery circuit breaker is open

and BATTERY when the battery circuit breaker is closed during normal operation. This block reads

BATTERY EQUALIZE when the battery equalize charge voltage is used to recharge the battery. This

block also shows BATTERY TEMPERATURE when the battery temperature sensor option is

installed. The Module Battery Disconnect (MBD) is shown to the right of this block. The status of the

circuit breaker is illustrated as open or closed.

Output Metering Displays

Item 4 - UPS Ratings: This block displays the UPS module part number and kVA rating. The UPS

output voltage and frequency are also displayed in this block. The output circuit breaker is shown to

the right of this block. The status of the circuit breaker is illustrated as open or closed.
Item 5 - Load: This block displays the total output power to the critical load in kVA and kW. The

critical load current per phase is also displayed in this block. Note that kW is not displayed when the

load is on the bypass line. During an overload condition, the time remaining before transfer is dis-

played at the bottom of the load box.

NOTE
All voltage readings are phase-to-phase measurements (A-B, B-C and C-A). All current

readings are phase measurements (A, B and C).

UPS INPUT PWR

480V 480V 480V

350A 350A 350A

BATTERY

VOLTS 540
AMPS 15 CHARG

UPS RATINGS

A-B B-C C-A

480V 480V 480V

60.0 Hz

AP658-64

RATED 500 KVA

OUTPUT VOLTAGE

BYPASS INPUT

A-B B-C C-A

480V 480V 480V

60.0 Hz

LOAD

A B C

270 KVA / 217 KW

325A 325A 325A

A-B B-C C-A

OK to Transfer
Static Switch Connected

2

3

5

4

6

7

1