CIRCUIT BREAKER AND FUSED DISCONNECT SWITCH SIZES

kW

VOLTS

PH

L1

L2

L3

Breaker or Fuse Size Copper Wire Size

Conduit Size

6

208

1

29

29

—

40

8

1/2”

208

3

14

25

14

40

8

3/4”

240

1

25

25

—

40

8

1/2”

240

3

13

22

13

30

10

1/2”

480

3

6

11

6

15

14

1/2”

9

208

1

43

43

—

60

6

3/4”

208

3

22

38

22

50

8

3/4”

240

1

38

38

—

50

8

1/2”

240

3

19

33

19

50

8

3/4”

480

3

9

16

9

20

12

1/2”

12

208

1

58

58

—

90

3

1”

208

3

33

33

33

50

8

3/4”

240

1

50

50

—

70

4

1”

240

3

29

29

29

40

8

3/4”

480

3

14

14

14

20

12

1/2”

15

208

1

72

72

—

90

3

1”

208

3

42

42

42

60

6

3/4”

240

1

63

63

—

90

3

1”

240

3

36

36

36

50

8

3/4”

480

3

18

18

18

30

10

1/2”

18

208

1

87

87

—

125

1

1-1/4”

208

3

48

48

48

60

6

3/4”

240

1

75

75

—

100

3

1”

240

3

43

43

43

60

6

3/4”

480

3

22

22

22

30

10

1/2”

24

208

1

115

115

—

150

1/0

1-1/4”

208

3

67

67

67

90

3

1-1/4”

240

1

100

100

—

125

1

1-1/4”

240

3

58

58

58

90

3

1-1/4”

480

3

30

30

30

40

8

3/4”

30

208

1

144

144

—

200

3/0

1-1/2”

208

3

83

83

83

125

3

1-1/2”

240

1

125

125

—

175

2/0

1-1/2”

240

3

72

72

72

100

3

1-1/4”

480

3

36

36

36

50

8

3/4”

36

208

1

173

173

—

225

4/0

2”

208

3

100

100

100

125

1

1-1/2”

240

1

150

150

—

200

3/0

1-1/2”

240

3

87

87

87

125

1

1-1/2”

480

3

43

43

43

60

6

3/4”

45

208

3

125

125

125

175

2/0

2”

240

1

188

188

—

250

250 MCM

2”

240

3

108

108

108

150

1/0

1-1/2”

480

3

54

54

54

70

4

1”

54

208

3

150

150

150

200

3/0

1-1/2”

240

3

130

130

130

175

2/0

2”

480

3

65

65

65

90

3

1-1/4”

58

208

3

162

162

162

225

4/0

2”

240

3

141

141

141

200

3/0

1-1/2”

480

3

71

71

71

90

3

1-1/4”

Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers are to be mounted remotely and wired by the contractor. Sizes are
based on the NEC table 310-16. Conduit size is based on conductors plus ground wire sizing as per NEC table 250-122.