Boiler dimensions & ratings – PB Heat MI/MIH series User Manual

Page 36

Advertising
background image

BOILER DIMENSIONS & RATINGS

10. BOILER DIMENSIONS & RATINGS

Table 10.2: Series MI/MIH Boiler Ratings

1 Net I=B=R water ratings based on an allowance of 1.15.

2 Consult factory before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation,

extensive piping systems, etc.

3 Heating Capacity and Annual Fuel Utilization Efficiency (AFUE) ratings are based on U.S. Government test.

MIH Models Available as Natural Gas with Intermittent Ignition Only.

Table 10.1: Series MI/MIH Boiler Dimensions

34

SERIES MI/MIH BOILER DIMENSIONS

Boiler
Model

Number

Jacket

Left of Jacket to

c/l of Vent “D”

Rear of Jacket to

c/l of Vent “E”

Vent Connector

Size “F”

Width

“A”

Depth

“B”

To Floor

“C”

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

MI/MIH-03

12

¹⁄₂

318

26

⁵⁄₈

676

31

³⁄₈

797

6

¹⁄₄

159

20

¹³⁄₁₆

529

5

127

MI/MIH-04

15

⁷⁄₈

403

26

⁵⁄₈

676

31

³⁄₈

797

7

¹¹⁄₁₆

195

20

¹³⁄₁₆

529

5

127

MI/MIH-05

19

¹⁄₄

489

26

⁵⁄₈

676

31

³⁄₈

797

9

⁵⁄₈

244

21

¹³⁄₁₆

554

6

152

MI/MIH-06

22

⁵⁄₈

575

26

⁵⁄₈

676

31

³⁄₈

797

11

⁵⁄₁₆

287

21

¹³⁄₁₆

554

6

152

MI-07

26

660

26

⁵⁄₈

676

31

³⁄₈

797

13

330

21

¹³⁄₁₆

554

7

178

MI-08

29

³⁄₈

746

29

⁵⁄₈

752

31

³⁄₈

797

14

¹¹⁄₁₆

373

23

⁵⁄₁₆

592

8

203

MI-09

32

³⁄₄

832

29

⁵⁄₈

752

31

³⁄₈

797

16

³⁄₈

416

24

⁵⁄₁₆

618

8

203

SERIES MI/MIH BOILER RATINGS

Boiler
Model

Number

Input

DOE Heating

Capacity³

Net I=B=R Ratings

Water¹,²

Seasonal

Efficiency

Std Pilot

w/Damper³

Seasonal

Efficiency

Intermittent

Ignition³

Water Content

MBH

kW

MBH

kW

MBH

kW

AFUE

AFUE

MI

MIH

MI

MIH

MI

MIH

MI

MIH

MI

MIH MI

MIH

MI

MIH

MI

MIH

Gallon

Liter

MI/MIH-03

70

65

21

19

58

54

17

16

50

47

15

14

80.2

N/A

82.2

83.2

4.72

17.87

MI/MIH-04

105

97.5

31

29

86

81

25

24

75

70

22

21

80.2

N/A

82.1

83.1

6.00

22.71

MI/MIH-05

140

130

41

38

115

108

34

32

100

94

29

28

80.2

N/A

82.0

83.0

7.28

27.55

MI/MIH-06

175

162.5

51

48

143

135

42

40

124

117

36

34

80.3

N/A

82.0

83.0

8.56

32.40

MI-07

195

N/A

57

N/A

160

N/A

47

N/A

139

N/A

41

N/A

80.5

N/A

82.0

N/A

9.84

37.24

MI-08

227.5

N/A

67

N/A

186

N/A

55

N/A

162

N/A

47

N/A

80.3

N/A

82.0

N/A

11.12

42.09

MI-09

260

N/A

76

N/A

211

N/A

62

N/A

183

N/A

54

N/A

80.1

N/A

82.0

N/A

12.40

46.93

Figure 10.1:Boiler Views

Advertising