SYMPTOM

POSSIBLE CAUSE

CORRECTIVE ACTION

Engine does not crank

Loose battery cables

• Check all battery cable connections

Defective battery

• Test battery. Replace as necessary.
• Check battery charger inline fuse

Improper battery charger function • Ensure charger is plugged into GFCI

receptacle
• Check for tripped GFCI receptacle. Reset if
required.
• Check for tripped breaker in branch circuit
supplying GFCI. Reset if required.
• Check all charger cable connections for
cleanness and tightness.
• Check charger lights to verify correct
operation. See Table A, Page 29.

Fault in starter signal circuit

• Contact a qualified generator dealer for service
assistance.

Blown control circuit fuse

• Check control circuit fuse.

Engine cranks without starting Low battery

• Test battery. Replace as necessary.
• Ensure charger is plugged into GFCI
receptacle
• Check for tripped GFCI receptacle. Reset if
required.
• Check for tripped breaker in branch circuit
supplying GFCI. Reset if required.
• Check all charger cable connections for
cleanness and tightness.
• Check charger lights to verify correct
operation. See Table A, Page 29.

Poor fuel supply

• Ensure all manual shutoff valves are open
• Check for proper fuel supply pressure
• Verify size and fill level of propane tank (LPG
only)
• Check fuel solenoid voltage during cranking

Low oil pressure

• Check engine oil level
• Check switch for proper function

High engine temperature

• Allow engine to cool, then restart
• Decrease loads on generator
• Check enclosure openings for blockage
• Check oil cooler for blockage

No generator output

Main line circuit breaker tripped

• Check breaker. Clear faults, then reclose
breaker.

Disconnect breaker tripped

• Check for tripped breaker in circuit between
generator output and transfer switch. Clear
fault, then reclose breaker.

Generator loss of excitation

• Contact a qualified generator dealer for service
assistance.

Excitation capacitor failure

• Contact a qualified generator dealer for service
assistance.

Generator diode or varistor failure • Contact a qualified generator dealer for service

assistance.

Generator head fault

• Contact a qualified generator dealer for service
assistance.

Engine starts then
immediately shuts down