Possible Cause

Remedy

Heater will not come on

Pump not running

Place pump in operation

Pump air locked

Check for leaks

Filter dirty

Clean filter

Pump strainer clogged

Clean strainer

Defective wiring or connection

Repair or replace wires

Defective pressure switch

Replace switch

Defective gas controls

Call serviceperson

On-Off switch in "OFF" position

Turn switch to "ON"

Heater Short Cycling

(Rapid On and Off Operation)

Insufficient water flow

Clean filter and pump strainer

Defective wiring

Repair or replace wiring

Defective flow valve or out of adjustment

Call serviceperson

Defective hi-limit and/or thermostat

Call serviceperson

Heater Makes Knocking Noises,
Make sure all valves on system are open

Heater operating after pump has shut off

Shut off gas supply and call serviceperson

Heater exchanger scaled

Shut off gas supply and call serviceperson

Troubleshooting - General

CAUTION

Please consult the latest edition of the “MiniMax Service Manual” for complete service and repair
instructions. Repairs should only be attempted by properly trained service personnel.