Installing the chassis ground connection, Connecting power to the os-10 system, Ground wire specifications – Patton electronic 1052 User Manual

Page 33: Os-10 power options

Advertising
background image

OnSite System Installation

33

OnSite Series Getting Started Guide

3 • Installation Overview

Installing the Chassis Ground Connection

The OS-10 system chassis requires a reliable earth ground connection. You must connect the chassis to a reli-
able earth ground. The ground wire must be installed in accordance with local electrical safety standards.

To connect the OS-10 system chassis to a reliable earth ground, follow these steps:

1. Strip one end of the ground wire to the length required for the ground lug or terminal.

Note

For the NEBS ground lug, the length is approximately 0.75 inches
(20 mm)

Note

For a user-provided ring terminal—as required

2. Crimp the ground wire to the ground lug or ring terminal, using a crimp tool of the appropriate size.

3. Attach the ground lug or ring terminal to the chassis grounding terminal location shown in Figure 3.

4. Connect the other end of the ground wire to a suitable grounding point at your site.

After installation and proper grounding of the OS-10 chassis, you can connect the following:

Power wiring

Cables for the fiber-optic interface and Category 5 cables for E1 and Ethernet client signal interfaces

Category 5 cables for the Ethernet LAN and SERIAL management ports

Connecting Power to the OS-10 System

The system supports AC and DC power options, as listed in

Table 7

. These options are factory installed.

Note

Both AC and DC options provide short-circuit and over-voltage pro-
tection.

Note

The DC option provides reverse input polarity protection.

Table 6. Ground Wire Specifications

Grounding Standard

Wire

EN/IEC 60950

AWG 18 (1 mm2) or larger wire and an
appropriate user-supplied ring terminal

NEBS

AWG 6 (13 mm2) wire and the ground
lug provided in the accessory kit

NEC (National Electric Code) AWG 14 (2 mm2) or larger wire and an

appropriate user-supplied ring terminal

Table 7. OS-10 Power Options

Power Options

Nominal Input

Tolerance Limit

Feature

AC

110 VAC at 50 Hz and
220 VAC at 60 Hz

100 to 245 VAC

Auto-switching AC to DC power converter

DC

–48VDC

–36 to –72 VAC

Auto-switching AC to DC power converter