602 Specification Table: Standard Product — FE and QFE 4.3KVA-18KVA

Model

4.3KVA/3kW

5.3KVA/3.7kW

7KVA/5kW

10KVA/7.5kW

12.5KVA/10kW

18KVA/15kW

AC Input Voltage
and Current,
Standard Charger


FE:


QFE:

100 = 38 amps
120 = 32 amps*
200 = 19 amps
208 = 18 amps
220 = 17 amps
240 = 16 amps
220 = 19 amps
230 = 18 amps
240 = 17 amps
380 = 11 amps
400 = 10 amps
415 = 9 amps

100 = 46 amps
120 = 38 amps*
200 = 23 amps
208 = 22 amps
220 = 21 amps
240 = 19 amps
220 = 21 amps
230 = 20 amps
240 = 19 amps
380 = 13 amps
400 = 12 amps
415 = 11 amps

100 = 58 amps
120 = 51 amps*
200 = 29 amps
208 = 30 amps
220 = 27 amps
240 = 26 amps
220 = 27 amps
230 = 26 amps
240 = 24 amps
380 = 16 amps
400 = 15 amps
415 = 14 amps

—
—
200 = 45 amps
208 = 45 amps
220 = 41 amps
240 = 39 amps
220 = 43 amps
230 = 41 amps
240 = 39 amps
380 = 25 amps
400 = 24 amps
415 = 23 amps

—
—
200 = 59 amps
208 = 58 amps
220 = 53 amps
240 = 50 amps
220 = 55 amps
230 = 53 amps
240 = 51 amps
380 = 33 amps
400 = 31 amps
415 = 30 amps

—
—
200 = 85 amps
208 = 86 amps
220 = 81 amps
240 = 76 amps
220 = 81 amps
230 = 78 amps
240 = 75 amps
380 = 48 amps
400 = 46 amps
415 = 44 amps

Recommended Input
Service for 60 Hz
Models**

120 = 40 amp*
208 = 25 amp
240 = 20 amp

120 = 50 amp*
208 = 30 amp
240 = 25 amp

120 = 65 amp*
208 = 40 amp
240 = 35 amp

208 = 60 amp
240 = 50 amp

208 = 75 amp
240 = 65 amp

208 = 115 amp
240 = 100 amp

Output Voltage and
Maximum Output
Current in amps***


FE:


QFE:

100 = 42 amps
120 = 34 amps
200 = 21 amps
208 = 20 amps
220 = 19 amps
240 = 17 amps
220 = 19 amps
230 = 18 amps
240 = 17 amps

100 = 52 amps
120 = 44 amps
200 = 26 amps
208 = 26 amps
220 = 24 amps
240 = 22 amps
220 = 23 amps
230 = 22 amps
240 = 21 amps

100 = 68 amps
120 = 58 amps
200 = 34 amps
208 = 34 amps
220 = 31 amps
240 = 29 amps
220 = 31 amps
230 = 30 amps
240 = 28 amps

100 = 98 amps
120 = 82 amps
200 = 49 amps
208 = 48 amps
220 = 46 amps
240 = 41 amps
220 = 45 amps
230 = 43 amps
240 = 41 amps

100 = 124 amps
120 = 103 amps
200 = 62 amps
208 = 58 amps
220 = 55 amps
240 = 51 amps
220 = 56 amps
230 = 52 amps
240 = 51 amps

100 = 176 amps
120 = 149 amps
200 = 88 amps
208 = 84 amps
220 = 82 amps
240 = 73 amps
220 = 84 amps
230 = 76 amps
240 = 73 amps

Efficiency On AC
Line

90%

90%

90%

90%

91%

92%

On Line BTU/hour:

KW/hour:

1138
.333

1403
.411

1896
.556

2844
.833

3375
.989

4452
1.3

Audible Noise (dB)

50

51

52

55

56

57

Runtime (minutes)

Full Load:
Half Load:

10
24

20
50

12
33

11
26

18
48

10
26

Weights:
Without Battery

60 Hz Units
50 Hz Units

With Battery****

60 Hz Units
50 Hz Units

N Cabinet with
Standard Batteries

243 lbs.
115.7 kgs.

348 lbs.
163.3 kgs.

—

268 lbs.
131.1 kgs.

484 lbs.
229.1 kgs.

—

362 lbs.
176.5 kgs.

578 lbs.
274.4 kgs.

—

442 lbs.
217.7 kgs.

—
—

395 lbs.
(179.2 kgs.)

505 lbs.
251.3 kgs.

—
—

535 lbs.
(242.7 kgs.)

625 lbs.
312.1 kgs.

—
—

675 lbs.
(306.2 kgs.)

Dimensions
(H x W x D)

29.5 in. x 15.5 in. x 25 in.
750 mm x 395 mm x 635 mm

NOTE: If your model has an internal

bypass switch, add 8 in. or
200 mm to the depth.

36.5 in. x 19 in. x 32 in.
930 mm x 485 mm x 815 mm

NOTE: If your model has an internal bypass switch, add 8 in. or 200 mm to

the depth.

* FE 4.3KVA, 5.3KVA and 7KVA models have optional 120 VAC input voltage.
** Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown are for the U.S. and
Canada.
***At 0.7 to 0.83 leading power factor.
****FE and QFE 10KVA, 12.5KVA and 18KVA models do not have internal batteries. Batteries are in a separate battery cabinet or rack.