Whichever termination is chosen, it must be double
wall vent certified under UL 1738, or ULC-636.
When installing a sidewall exhaust system the
termination must be backed by a metal plate secured to
the wall as shown in the figure.

Correct rain cap,

unrestricted.

Typical incorrect

rain cap.

If the exhaust vent is routed through the roof, the
termination must be either the same type as described
for a sidewall installation or a rain cap. The preferred
method to terminate the exhaust vent is with a rain cap
to minimize the drippage of condensate onto the roof
and ice build-up

.

The rain cap should be an

unrestrictive type similar to the figure above. Elbows
are also acceptable.

3.4.5 Equivalent Length of Fittings

Fitting Description

Equivalent Length

90º Elbow

10 feet

45º Elbow

5 feet

Rain Cap

10 feet

Boot Tee/135º Tee

10 feet

Standard Tee Used as a
Vent Termination

10 feet

3.4 C

LEARANCES

In addition to any clearance requirements in Sections
3.1 and 3.3 the following clearances must be
maintained for inlet and vent components.

3.4.1 Sidewall Installations

Combustion

Air Intake

2' to snow

line

Flue Gas
Outlet

Flue Gas

Outlet