Connecting dryer using 4-wire connection, Exhaust information – Panasonic VA-12020 User Manual

Page 3

Advertising
background image

REMOVE GROUND STRAP AND DISCARD
KEEP GREEN GROUND SCREW

RELOCATE GREEN GROUND

SCREW HERE

strain relief

bracket

HOT

NEUTRAL

(white)

3/4", UL

recognized

strain relief

HOT

• Remove the cover near the power cord entry hole.

• Install 3/4" UL recognized strain relief to power

cord entry hole. Bring power cord through strain

relief.

• Connect two HOT lines to outer screws (L1 & L2)

of terminal block.

• Connect NEUTRAL (white) line to center screw (N)

of terminal block.

• Attach ground wire of the power cord with the

green ground screw (hole above strain relief bracket).

• Tighten all terminal block screws firmly.

• Properly secure power supply cable to strain relief.

• Reinstall the cover.

CONNECTING DRYER USING 4-WIRE CONNECTION

REAR EXHAUST LOCATION

The dryers come ready for rear exhausting. Units

have separate exhausts.

EXHAUST LENGTH

EXHAUST INFORMATION

MAXIMUM LENGTH

EXHAUST

– HOOD TYPE –

A

B

NUMBER

OF 90˚

TURNS

RIGID METAL DUCT

0

45 ft.

30 ft.

35 ft.

20 ft.

4" DIAMETER

2

25 ft.

10 ft.

PARTS AVAILABLE FROM LOCAL SERVICE

ORGANIZATION

• Rigid Metal Duct Components

WX8X63 4" X 1' Duct

WX8X64 4" x 2' Duct

WX8X51 4" Elbow

WX8X59 4" Aluminum Hood

• Flexible Metal Duct Components

WX08X10077 4" dia. flexible metal (semi-rigid)

UL-listed transition duct (includes 2 elbows)

CAUTION

: F

or personal safety this appliance

must be properly grounded.

WARNING

:

Never leave the terminal block without the cover.

WARNING

:

Only a 4-conductor cord shall be used when the

appliance is installed in a location where grounding through the

neutral conductor is prohibited. Grounding through the neutral is

prohibited for the new branch-circuit installations, mobile homes,

recreational vehicles, and areas where local codes prohibit

grounding through the neutral conduction.

The MAXIMUM ALLOWABLE duct length and number of

bends of the exhaust system depends upon the type of duct,
number of turns, the type of exhaust hood (wall cap), and all
conditions note below. The maximum allowable length for
rigid metal duct is shown in the
table below. More than two 90˚
turns is not recommended. The
total length of flexible metal duct
shall not exceed 8 ft.(2.4 m). In
Canada and in the United States,
the required exhaust duct diameter
is 4in (102mm).

WARNING - TO REDUCE THE RISK OF

FIRE OR PERSONAL INJURY:

Provide an access for inspection and cleaning of the

exhaust system, especially at turns and joints.

Exhaust system shall be inspected and cleaned at

least once a year.

Do not obstruct incoming or exhausted air.

Do not assemble ductwork with any fasteners that

extend into the duct. These fasteners can accumul-

ate lint, creating a potential fire hazard.

In special installations, it may be necessary to connect

the dryer to the house vent using a flexible metal (foil-

type) duct. A UL-listed flexible metal (foil-type) duct

may be used ONLY in installations where rigid metal or

flexible metal (semi-rigid) ducting cannot be used AND

where a 4” diameter can be maintained throughout the

entire length of the transition duct. In Canada and in

the United States, only the flexible metal (foil-type)

ducts that comply with the “Outline for Clothes Dryer

Transition Duct Subject 2158A” shall be used.

Never install a screen in or over the exhaust duct.

This will cause lint to accumulate, creating a poten-

tial fire hazard.

Do not use duct longer than specified in the exhaust

length table. Longer ducts can accumulate lint,

creating a potential fire hazard.

Never terminate the exhaust into a common duct

with a kitchen exhaust system. A combination of

grease and lint creates a potential fire hazard.

Do not terminate exhaust in a chimney, a wall, a ceil-

ing, gas vent, crawl space, attic, under an enclosed

floor, or in any other concealed space of a building.

The accumulated lint could create a fire hazard.

Use only 4” rigid metal or UL-listed flexible metal

(semi-rigid or foil-type) duct to connect the dryer to

the home exhaust duct. It must be installed in

accordance with these instructions and local codes.

Use only 4” rigid metal ducting for the home exhaust

duct.

This clothes dryer must be exhausted to the outdoors.

4 #10 AWG MINIMUM COPPER CONDUCTORS OR 120/240V 30A
POWER SUPPLY CORD KIT MARKED FOR USE WITH DRYERS &
PROVIDED WITH CLOSED LOOP OR SPADE TERMINALS WITH
UPTURNED ENDS (NOT SUPPLIED).