Chapter 2-First Time Installation and Configuration

2-16

3

Remove the transparent plastic caps on the terminal block.

4

Using the two wires of an 10 AWG cable running from the DC power

distribution unit, connect the black wire into the -48VDC terminal
block and the red wire to the RTN terminal block.

5

Connect the green or green-yellow wire to the system single-point
M6x15 “Ground” bolt.

•

A 10 AWG cable must be used to connect the mains with the RMX 4000 DC
Power Rail Model.

•

The supply wires for DC version must be terminated using quick connectors.

•

Extension cords may not be used.

ESD connector

Circuit breaker - ON

position

-48 VDC

RTN

Ground connector

Blank panel

Circuit breaker - OFF

position

The center PRM slot/module is fitted with a blank panel and the slot cannot be
used on a system with DC Voltage.

The rating of the protective earthing conductor should be a minimum of 10AWG.