Powerware 9150 User Manual

Page 33

Advertising
background image

Installation

29

Powerware

®

9150 User’s Guide

:

www.powerware.com

Powerware 9150 Hardwired Terminations for Optional PDM

Wire Function

Terminal

Upstream

Suggested Wire Size**

Conduit Connection

Input

Terminal

Position*

Upstream

Circuit Breaker

Suggested Wire Size**

Conduit Connection

(Entry Size)

Ground

TB1-1

8 AWG

L1/A

TB1-2

70A

4 AWG

1-3/4

2 access hole for

L2/B

TB1-3

70A

4 AWG

1-3/4 access hole or

1-1/4

2 conduit

Neutral

TB1-4

2 AWG

Output for PDM

Wire Color

Ground

TB1-6

Green/Yellow

L1/A

TB1-7

Black

1-3/4

2 access hole for

L2/B

TB1-8

Red

1-3/4 access hole or

1-1/4

2 conduit

Neutral

TB1-9

White

*All terminal wire size ratings are 8 - 4 AWG, except TB1-4 is 8 - 1/0.
**Use 75

•C copper wire. Suggested wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.

NOTE Proper phase rotation must be observed.

1

2

3

4

6

7

8

9

Ground L1/A

L2/B

N

Ground L1/A L2/B

N

Input

Output

Figure 11. Hardwired Terminal Blocks