Powerware 9395 UPS and Plus 1 UPS 650825 kVA User Manual

Page 100

Advertising
background image

INSTALLING OPTIONS AND ACCESSORIES

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

5−8

Table 5-4. Pull−Chain Wiring Terminations with MOBs

From

To

Function

UPS 1 CAN Bridge Card J3–1 (Alarm)

MOB 1 Aux 1 NC

MOB Open Alarm

UPS 1 CAN Bridge Card J3–2 (Alarm Return)

MOB 1 Aux 1 Com

UPS 1 TB2–1 (Pull Chain)

MOB 1 Aux 2 NO

Pull Chain

UPS 1 TB2–2 (Pull Chain Common)

UPS 2 TB2–2 (Pull Chain Common)

Pull Chain Common

UPS 2 CAN Bridge Card J3–1 (Alarm)

MOB 2 Aux 1 NC

MOB Open Alarm

UPS 2 CAN Bridge Card J3–2 (Alarm Return)

MOB 2 Aux 1 Com

UPS 2 TB2–1 (Pull Chain)

MOB 2 Aux 2 NO

Pull Chain

UPS 2 TB2–2 (Pull Chain Common)

UPS 3 TB2–2 (Pull Chain Common)

Pull Chain Common

UPS 3 CAN Bridge Card J3–1 (Alarm)

MOB 3 Aux 1 NC

MOB Open Alarm

UPS 3 CAN Bridge Card J3–2 (Alarm Return)

MOB 3 Aux 1 Com

UPS 3 TB2–1 (Pull Chain)

MOB 3 Aux 2 NO

Pull Chain

UPS 3 TB2–2 (Pull Chain Common)

UPS 4 TB2–2 (Pull Chain Common)

Pull Chain Common

UPS 4 CAN Bridge Card J3–1 (Alarm)

MOB 4 Aux 1 NC

MOB Open Alarm

UPS 4 CAN Bridge Card J3–2 (Alarm Return)

MOB 4 Aux 1 Com

UPS 4 TB2–1 (Pull Chain)

MOB 4 Aux 2 NO

Pull Chain

MOB 1 Aux 2 Com

MOB 2 Aux 2 Com

Pull Chain MOB Common

MOB 2 Aux 2 Com

MOB 3 Aux 2 Com

MOB 3 Aux 2 Com

MOB 4 Aux 2 Com

Advertising