Table 3-3. fault configuration for fault alarm – Hamilton Sundstrand Company Gas Fuel Metering Valve HFG2.0 User Manual

Page 54

Advertising
background image

48 HFG2.0

USER

GUIDE

Fault Alarm Type

Persist Time

Fault Action


Driver Over Current

10 Sec


1 Sec

Driver current > Max Force equivalent

current, Fault.

Driver current > Max Force equivalent

current, Fault. If persists for 1 Min.,

Shutdown

Driver current > 18 Amps, Fault. If

persists for 1 Min., Shutdown


Tracking Error

10 Sec

If in RUN state, not in home dead band

and position error > allowable,

Fault.

If not in overcurrent, RDC not faulted and

feedback not equal to demand, Fault.

Watchdog Expired

< 1 Sec

If last reset was caused by watchdog

timer timeout or illegal address attempt,

Fault.

RDC Failure

< 1 Sec

Tests hardware for RDC failure, sets

Fault if RDC failure bit set.

Retract/Extended

Command

N/A

Fault not used.

Unregulated Voltage Low

10 Sec

Unregulated voltage low, Fault.

+14 Volts Low

7.5 Sec

< 1 Sec

+14 V supply < 12 V, Fault.

+14 Volts High

7.5 Sec

< 1 Sec

+14 V supply > 16 V, Fault.

-14 Volts Low

7.5 Sec

< 1 Sec

-14 V supply > -12 V, Fault.

-14 Volts High

7.5 Sec

< 1 Sec

-14 V supply < -16 V, Fault.

Input Voltage Low

7.5 Sec

< 1 Sec

Input Voltage < 75 V, Fault.

Input Voltage High

7.5 Sec

< 1 Sec

Input Voltage > 180 V, Fault.

DSP Failure

N/A

Fault not implemented.

Electronics Over Temp

10 Sec

Electronics

temp

≥ 110 °C, Fault

Table 3-3. Fault Configuration For FAULT Alarm