SYMPTOM

POSSIBLE CAUSE

CORRECTIVE ACTION

Low generator output voltage

Low engine speed

• Verify correct engine speed. Remove excess
loads or adjust speed as required.

Excitation capacitor failure

• Contact a qualified generator dealer for service
assistance.

Generator diode or varistor failure • Contact a qualified generator dealer for service

assistance.

Overspeed light stays lit

Shutdown due to high engine
speed

• Verify correct engine speed setting. Adjust
engine speed as required.

Underspeed light stays lit

Shutdown due to low engine
speed

• Reduce loads connected to generator

• Check engine speed setting at no load.
Adjust as required.

Overcrank light stays lit

Failure to start

• See "Engine cranks without starting"

Not In Auto light stays lit

Generator not set for unattended
operation

• Place mode switch into AUTO position if
automatic function is required

Low oil pressure light stays lit Shutdown due to low engine oil

pressure

• Check engine oil level.

• Verify correct type of engine oil for ambient
temperature conditions

Low battery light stays lit

Low battery

• Test battery. Replace as necessary.
• Ensure charger is plugged into GFCI
receptacle
• Check for tripped GFCI receptacle. Reset if
required.
• Check for tripped breaker in branch circuit
supplying GFCI. Reset if required.
• Check all charger cable connections for
cleanness and tightness.
• Check battery charger inline fuse
• Check charger lights to verify correct
operation. See Table A, Page 29.

Blown charger circuit fuse

• Check engine alternator fuse

High engine temperature light
stays lit

Shutdown due to high engine
temperature

• Allow engine to cool, then restart

• Decrease loads on generator
• Check enclosure openings for blockage
• Check oil cooler for blockage