Premier Heat Pumps – Water Heater and Chiller Manual

Page 17

minutes.

2) Parameters for Exiting Defrost Mode:
• When defrosting time reach 3 minutes and T4 reaches 10°C or defrosting

time reaches 8 minutes, defrost exits and starts heating water mode.
While defrost is exiting, after compressor and fan motor have stopped for
1 minute, the four way valve1 is turned off.

• The Compressor will restart after it stops for 3 minutes, and the system

will run the same mode as before defrosting.

5-3 Fault Codes and Fault Descriptions


Failure Code:

E1:

sensor for T1 (water temperature) failure

E2:

sensor for T2 (ambient temperature) failure

E3:

sensor for T3 (exhaust temperature from compressor) failure

E4:

sensor for T4 (coil temperature in condenser) failure

E5:

Compressor stops three times in 24 hours because the current is too high.

E6:

While heating water, there is three times of T3≥100°C in 24 hours.

E7:

There is electrical leakage in the compressor or outdoor motor or four-way

valve

Recommendation: Contact the installer or service agent

6 - Maintenance Instructions

The following operational maintenance must be done by a qualified person each
year:

• Clean the back evaporator with a delicate brush and water jet without

any pressure (karcher prohibited)

• Check the mandatory labelling and the operation of the unit

• Check the safety measures

• Check the pressure of the refrigerating gas

• Clean the electric box and control the connections

• Check the electrical connections