Nordyne Single Package Heat Pump R-410A User Manual

Page 11

Advertising
background image

11

Diagnostic Description

LED Status

Control Fault (No Power)

Off

Normal Operation

On

ASCD Delay Active
(with compressor demand)

1 Flash

Low Pressure Switch Lockout

2 Flashes

High Pressure Switch Lockout

3 Flashes

Ambient Sensor Fault

4 Flashes

Coil Sensor Fault

5 Flashes

Table 3. Control Diagnostic

Star Bushing

Bolt

Nut

Ambient Sensor

Plastic Clip

Nut

Figure 10. Ambient Sensor Mounting

Control is uncalibrated when power is applied.
Calibration occurs after a defrost cycle. The
control initiates defrost after 34 minutes of
accumulated compressor run time in heating
with coil temperature below 35° F. The defrost
cycle terminates when the coil sensor reaches
termination temperature or after 14 minutes.
Note: All units are shipped from the factory
with the default termination temperature set
at 70° F.

Defrost function is disabled if coil temperature is
above 35° F. If the ambient sensor is detected as
open or shorted, demand defrost will not operate
and control will revert to time/temperature defrost
operation. If the outdoor coil sensor is detected
as open or shorted, the control will not perform
demand or time/temperature defrost operation.
Note: When the defrost cycle initiates, there
will be a 30 second compressor delay going
into and out of the defrost cycle. This delay may
be removed by removing P6 connector on the
board.

This 2-stage unit will defrost in second stage
regardless of the stage called for by the
thermostat.

6. Install one spacer next between the

p l a s t i c c l i p a n d m o u n t i n g b ra cke t .

7. Bend the mounting bracket into position.

Install the mounting bracket to the unit
using the screw in the corner panel.

Electric Heat Package (optional)
This heat pump is shipped without an auxiliary
electric heat kit installed. If electric heat is desired,
an accessory Heater Kit must be fi eld installed.
See Specifi cations Sheet for available kits and
their application.
• Select the correct size heat package for the

installation.

• Follow installation instructions provided with

each heater kit.

• Installation is most easily accomplished before

making duct or electrical connections.

• Refer to Table 2 (page 10) for blower

speeds.

Ambient Sensor Mounting
For optimum performance of the heat pump
system, the ambient sensor (Figure 10) must
be mounted on the outside of the unit.
1. Remove the mounting bracket and all

h a r d w a r e i n c l u d e d i n t h e p a cke t .

2.

R e m o v e s t a r b u s h i n g f r o m 7 / 8 ”
h o l e i n c o r n e r p a n e l o f t h e u n i t .

3. Route the ambient sensor through the 7/8”

hole in the corner panel of the unit, and then
through the 7/8” hole in the mounting bracket.

4.

R o u t e t h e s e n s o r t h r o u g h t h e
star bushing. Use the star bushing to
secure the mounting bracket to the unit.

5. Secure the ambient sensor inside the

plastic clip and secure it to the mounting
bracket with the screw and nut provided.

Advertising